IOM VLH VLC 704 1204

Page 50
Technical data
Compressor electrical data
VLH/VLC 704 804 904 1004 1104 1204
Number
4 4 4 4 4 4
Nominal power input kW
(12,3+15,5)
x2
(15,5+15,5)
x2
(15,5+19,3)
x2
(19,3+19,3)
x2
(19,3+25,6)
x2
(25,6+25,6)
x2
Max. absorbed power kW
(17,0+21,6)
x2
(21,6+21,6)
x2
(21,6+27,1)
x2
(27,1+27,1)
x2
(27,1+36,0)
x2
(36,0+36,0)
x2
Rated current A
(24,0+26,0)
x2
(26,0+26,0)
x2
(26,0+34,0)
x2
(34,0+34,0)
x2
(34,0+44,0)
x2
(44,0+44,0)
x2
Max current A
(34+36,7)
x2
(36,7+36,7)
x2
(36,7+48,7)
x2
(48,7+48,7)
x2
(48,7+65,4)
x2
(65,4+65,4)
x2
Oil pan resistor W
(75+75)
x2
(120+120)
x2
(120+150)
x2
(150+150)
x2
(150+150)
x2
(150+150)
x2
VLH/VLC HPF 704 804 904 1004 1104 1204
Rated voltage V/ph/Hz 400 (±10%) /3/50
Max. absorbed power kW 86,4 95,7 109,8 120,8 138,6 156,4
Rated current A 114,52 116,76 137,78 154 174,5 195
Max. current FLA A 155,8 161,2 190 214 247,4 280,8
Max. start-up current LRA A 359,1 364,5 428,3 452,3 492 525,4
External fuses A 250 250 250 250 315 315
Max. cable section (*) mm
2
3x120 3x120 3x120 3x120 3x185 3x185
Exchanger resistance
Rated voltage V/ph/Hz 230/ (± 10%)/1/50
Max. absorbed power W 130
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.