IOM VLH VLC 704 1204

Page 48
8.3 Unit electrical data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
VLH/VLC STD 704 804 904 1004 1104 1204
Rated voltage V/ph/Hz 400 (±10%) /3/50
Max. absorbed power kW 82,8 92,1 105 116 133,8 151,6
Rated current A 111,82 114,06 134,18 150,4 170,9 191,4
Max. current FLA A 153,1 158,5 186,4 210,4 243,8 277,2
Max. start-up current LRA A 356,4 361,8 424,7 448,7 488,4 521,8
External fuses A 250,0 250,0 250,0 250,0 315,0 315,0
Max. cable section (*) mm
2
3x120 3x120 3x120 3x120 3x185 3x185
Exchanger resistance
Rated voltage V/ph/Hz 230/ (± 10%)/1/50
Max. absorbed power W 130
Technical data
VLH/VLC L 704 804 904 1004 1104 1204
Rated voltage V/ph/Hz 400 (±10%) /3/50
Max. absorbed power kW 82,8 92,1 105 116 133,8 151,6
Rated current A 111,82 114,06 134,18 150,4 170,9 191,4
Max. current FLA A 153,1 158,5 186,4 210,4 243,8 277,2
Max. start-up current LRA A 356,4 361,8 424,7 437 488,4 521,8
External fuses A 250,0 250,0 250,0 250,0 315,0 315,0
Max. cable section (*) mm
2
3x120 3x120 3x120 3x120 3x185 3x185
Exchanger resistance
Rated voltage V/ph/Hz 230/ (± 10%)/1/50
Max. absorbed power W 130
VLH/VLC S 704 804 904 1004 1104 1204
Rated voltage V/ph/Hz 400 (±10%) /3/50
Max. absorbed power kW 82,8 92,1 105 116 133,8 151,6
Rated current A 111,82 114,06 134,18 150,4 170,9 191,4
Max. current FLA A 153,1 158,5 186,4 210,4 243,8 277,2
Max. start-up current LRA A 356,4 361,8 424,7 437 488,4 521,8
External fuses A 250,0 250,0 250,0 250,0 315,0 315,0
Max. cable section (*) mm
2
3x120 3x120 3x120 3x120 3x185 3x185
Exchanger resistance
Rated voltage V/ph/Hz 230/ (± 10%)/1/50
Max. absorbed power W 130