IOM VLH VLC 704 1204

Page 46
Technical data
VLC HT 704 804 904
Power supply V/ph/Hz 400 (±10%) / 3 / 50
Number of circuits 2 2 2
Capacity steps % 20-50-70-100 25-50-75-100 28-50-78-100
Refrigerant
Type / GWP R410A / 2.088
Charge 1/2
(1)
kg 21,5/21,5 24,5/24,5 27/27
tCO
2
eq 44,9/44,9 51,2/51,2 56,4/56,4
Compressor
Type Scroll
Number 4 4 4
Start-up type Direct
N°of loading stages 0/100 0/100 0/100
Condenser
Type Coil
Refrigerant connections
Inlet diameter inch 7/8” 7/8” 1 1/8”
Outlet diameter inch 15/8” 15/8” 2 1/8”
Weights
Shipping weight kg 1402 1529 1613
Additional Weights
Desuperheater versions kg 20 20 30
With one pump kg 85 85 90
With two pumps kg 200 200 205
Copper Fins kg 520 520 520
Dimensions
Length mm 4300 4300 4300
Width mm 1100 1100 1100
Height mm 2300 2300 2300
(1) The value is representing the contribution to the global refrigerant charge given by the standard unit only. Contribution of connection piping and remote evaporator
is not included here.