IOM SYSLOOP (IOM SL 01 S 3GB)

Table Of Contents
English
Seeing
"under tension"
Seeing
"fault reporting"
25SYSLOOP
Place the plugs back on the valves and check that they are properly tightened.
If needed, x the cables and the pipes on the wall with clamping collars.
Operate the SYSLOOP in the presence of the user and explain all functions.
Show him how to remove, clean and place back the lters.
17. FINAL TASKS
18. STARTING - RECOMMENDATIONS - SETTINGS
1. Check that all the water valves are open and that water circulates in the appliance before making
any demand for heating or cooling.
2. Ensure that the units are connected correctly to the mains power supply (Refer to the §
ELECTRICAL POWER SUPPLY, page 8 and in § WIRING DIAGRAM, page XII) f
3. Before attempting any start-up, ensure that the air and water temperatures are within the
appliances operating limits (in § OPERATING LIMITS, page 7).
4. Rotate the fan by hand to ensure that it turns freely and that the fan turbine is properly attached
to the motor shaft.
5. Check that the condensates drainage pipe is properly attached and free of any blockages.
6. Check the correct positioning of the lters and that they a clean and accessible.
7. Ensure that the nned heat exchanger surfaces are clean. Clean if required.
8. Check that the connection hoses are correctly tted and ensure that the appliances water circuit
has been correctly bled of any air.
9. Ensure that no Alarm code is displayed when the mains power supply is switched on (Refer to the
§ ALARM CODES, page 29).
10. Carry out the usual checks on the main water loop and particularly to ensure that the water
circulation pump operates correctly.
Non-compliance with this rule may result in irreversible damage. In addition, we recommend
the use of a ow controller on the units inlet pipe (not supplied).
Caution