Control Features
All SYSLOOP water source heat pumps are, in their standard version,
equipped with a Siemens POL423 electronic control system which
manages their operation and their safety devices.
The conguration of the POL423 electronic control enables four
different operating modes for water source heat pumps by selecting
the following systems :
Thermodynamic cooling and heating operation;
Thermodynamic cooling and heating operation or heating
operation with an additional electric heater;
Thermodynamic cooling operation and electrical heating
operation;
Thermodynamic cooling operation only.
POL822 remote control
An POL822 remote control is supplied as optional in the electrical
control box of the units.
It enables individually controlled operation or stand-alone regulation.
The POL822 remote control is ergonomically designed and discreet. It
comprises a digital display and essential functions such as :
On/Off,
Selection of operating mode,
Room temperature display,
Fan speed selection,
Temperature set-point adjustment
Alarm code display
Master/slaves control : the standard version of the POL423 electronic
control enables operation in master/slaves regulation mode for up to
15 water source heat pumps using a single POL822 remote control.
Thiscongurationenablestheinstallertosaveonthepurchaseand
wiring of equipment such as auxiliary relays and multi-wire cables
between the various water source heat pumps. Only a bus cable with
2 twisted pairs is necessary between the master and slave units.
Anti-freeze safety function : this is provided by two temperature
sensors. In cooling mode an "ICT" temperature sensor located in the
nned coil protects thewater source heat pump against accidental
freezing.
In heating mode, the safety function is provided by an "LWT" minimum
water outlet temperature sensor.
The automatic reset LP pressure switch completes the anti-freeze
safety function by monitoring a minimum acceptable suction pressure
to ensure correct operation of the compressor.
High temperature safety function : the "ICT & LWT" temperature
sensorscheck thatthe condensationtemperatureat thennedcoil
and the water temperature at the outlet of the water/refrigerant heat
exchanger do not exceed the authorised limits.
The automatic reset HP pressure switch completes the high
temperature safety function.
Electric heater : SYSLOOP water source heat pumps can be factory
equipped with an optional in-duct air heater located at the fan outlet.
The electric heaters are also available in kit.
The electricheater functioncan, dependingon thecongurationof
the POL423 electronic control, be used in place of the thermodynamic
heating as soon as the temperature in the water system drops below
a minimum limit, or it can be used as an electric heating system on
its own.
Units are factory equipped with two electric heater stages.