IOM SyScroll 140 360 Air EVO 361549

50
SYSCROLL AIR EVO TR 140 170 230 260 280 300 330 360
Power supply V/ph/Hz 400V/3/50Hz
Total capacity steps %
25-50-
75-100
25-50-
75-100
19-38-
69-100
17-39-
67-100
16-37-
68-100
24-48-
71-100
23-50-
73-100
25-50-
75-100
REFRIGERANT
Type / GWP R410A / 2.088
Charge Circuit One (1)
kg 23 23.5 27 28 28 43 53 54
tCO
2
eq 48.0 49.1 56.4 58.5 58.5 89.8 110.7 112.8
Charge Circuit Two (1)
kg 23 23.5 42.5 52 54 55 53 54
tCO
2
eq 48.0 49.1 88.7 108.6 112.8 114.8 110.7 112.8
COMPRESSOR
Number 4 4 4 4 4 4 4 4
Type / Oil type Scroll / POE
N° of loading stages 0/100 0/100 0/100 0/100 0/100 0/100 0/100 0/100
EVAPORATOR
Number 1 1 2 2 2 1 1 1
Type Plate
Water flow m
3
/h 24.5 29.3 39.8 45.0 49.0 53.2 55.9 62.1
Water pressure drop kPa 26 38 35 34 41 30 33 41
Water volume l 11.4 11.4 21.1 23.4 23.4 32.4 32.4 32.4
Inlet/outlet water connection inch 2”1/2 / 2”1/2 3” / 3”
RECOVERY CONDENSER
Number 1 1 2 2 2 1 1 1
Type Plate
Water flow m
3
/h 31.3 37.6 50.8 57.5 62.5 67.9 71.7 79.5
Water pressure drop kPa 43 62 57 56 67 49 54 67
Water volume l 11.4 11.4 21.1 23.4 23.4 32.4 32.4 32.4
Inlet/outlet water connection inch 2”1/2 / 2”1/2 3” / 3”
WEIGHT
Shipping kg 1.331 1.375 2.081 2.348 2.411 2.696 2.879 3.043
Operating kg 1.342 1.386 2.109 2.379 2.442 2.834 3.018 3.182
ADDITIONAL WEIGHT
EC versions kg 30 30 50 60 60 70 80 80
DIMENSIONS
Length mm 4.000 4.000 3.500 3.500 3.500 4.550 4.550 4.550
Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150
Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
8 - Technical Data (continued)
(1) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.