IOM SyScroll 140 360 Air EVO 361549

30
6 - Control
6 General information
Introduction
This document contains the information and the operating instructions
for 4 compressors & electronic control.
This information is for the after-sales service and the production
operators, for the end-of-line testing.
Main characteristics
Microprocessor control
User-friendly keyboard
Proportional and integral control of the return water temperature
(RWT)
Hysteresis control of the leaving water temperature (LWT)
Access code to enter the Manufacturer’s Level
Access code to enter the Service Level
Alarm and LED
Backlighted LCD
Pump-Down logic
Rotation of the compressor operation
Oil return function
Night mode (or Low Noise) control
Counting of the pump/compressors’ hours of operation
Display of discharge and suction pressure values
Display of temperature sensor
History of stored alarms (option)
Built-in serial Communication RS485 Card; to connect the
“Chiller Control” to a BMS network
The following accessories can be also connected:
Remote Display Terminal
Wire Remote Control.
6.1 Control with 4 compressors. The “CHILLER
CONTROL” system
The machines with 4 scroll compressors are provided with a
microprocessor card which is fully programmed by default for the
control of a chiller of cold only type with 2 circuits, 2 compressors per
circuit, a high-pressure transducer per circuit.
The control system consists of:
Keyboard & Display Terminal
General information
The figure shows the terminal with the front door open.
It is provided with a LCD 8 lines x 22 columns, keyboard and
microprocessor-controlled LED’s, so as to allow the programming of
the control parameters (setpoint, differential bands, alarm thresholds)
and themain operations to be carried out by the user.
Terminal & Key Board description
The terminal makes it possible to carry out the following operations:
– the initial configuration of the machine
– the change of all the main operating parameters
– the display of the detected alarms
– the display of all the measured quantities
The terminal and the card are connected by a 6-way phone cable.
The connection of the terminal to the basic card is not essential for
the normal operation of the controller.