10.1 Transport
The fans are supplied on wooden pallets they are packed in plastic foil. Transport the fan to the place of
assembly in its original packaging.
Do not transport the devices on the connection wire, the terminal box, the rotor, the protective grid or the
admission nozzle.
Load and unload the fan carefully, in order to avoid possible damage.
Use suitable lifting equipment. Use a four point suspension with straps in crane transport.
In transport and loading, pay attention to the weight of the fan.
Guidelines (without accessories) can be seen from the following table:
Upon receipt, carry out a visual check of the fan and examine the consignment for completeness.
10.2 Storage
NOTE
Risk of damage to the fan!
If it is stored for more than 3 months, turn the rotor by hand at intervals of 14 weeks.
In the packaging is intact (PE foil with space under the base) and without formation of condensation, the fans
can be stored out in the open for up to a month.
Unpacked fans may not be stored out in the open.
In dry, aired rooms without the risk of formation of condensation, the fans can be stored for a maximum of up
to 6 months.
If the period of storage is longer than 3 months, the rotor must be turned by hand at intervals of 4 weeks.
Storage temperatures:
–20 °C up to max. 60 °C
Size approx. weight with min./max. motor output in kg
KVB/F
9/9
10/10
12/12
15/15
18/18
20/20
22/22
25/25
30/28
11
AX - 12.2012
Smoke and heat exhaust fans