Installation Silencer
The fans have suitable sealing measures. However, the manufacturer assumes no warranty for connections
by the customer. When the fans are tted, the operator of the system must carry out a leakage test of the
system (before commissioning!) in accordance with legal requirements.
The complete channel system via which smoke and re gases are exhausted must full the required re resis-
tance classes according to local regulations.
When tting the exible connections, make sure that they are tted according to the stretched length (see
following table), without congestion or tensile strain. They are not used to compensate any lack of precision in
the assembly.
Install the exible connections offset, so that there is no reduction in efciency or a development of noise.
flow cage
perforated sheet
diffusor with inner core
flow cage
perforated sheet
diffusor with inner core
47
AX - 01.2013
Axial, smoke and heat exhaust fans, series AX