IMO AXC 2014 04
To ensure achievement of the characteristic, it is necessary for an even and irrotational ow to be available at
the inlet.
This is achieved in free intake by the addition of an admission nozzle or a stretch of channel with a length of
no less than 2.5 x D.
If this is not possible for construction reasons, a deector with bafe sheets arranged in front of the fan must
be optimised in its ow engineering properties in such a way that an even distribution of speed is achieved at
the fan inlet.
On the pressure side, a channel or tube with a length of no less than 2.5 x D is to be provided in order to
achieve the characteristic.
Contact with rotating parts must be ruled out at all times – either by channels of a corresponding length or by
protective grids.
Please consider also our proposal about the fan installation situation, see below mentioned.
Installation close to wall or ceiling
Installation duct
min. 1xD
1xD
flexible connection
min. 2,5xD
flexible connection
bellmouth
protection guard
min. 2,5xD
D = nominal diameter
46