NOTE Risk of damage to the fan!
The fan housing may not be deformed during assembly.
Carry out the assembly carefully!
NOTE Risk of damage to the fan!
Check by hand whether the rotor can be moved freely!
Do not t the fan if the rotor cannot be moved freely. Notify the manufacturer.
NOTE Risk of damage to the fan!
Prevent foreign bodies from being sucked in.
NOTE Risk of damage to the fan!
If the ow gets jammed, there is the risk of overheating.
Guarantee uninhibited and even owing into the appliance and free blowing out.
• If the gap dimensions are correct, t the fan in such a way that the impeller cannot be touched
during operation.
• Provide the fan at least with an IP 20 protective grid with free intake and free blow-out.
• Prevent the possibility of foreign bodies being taken in!
• Guarantee uninhibited and even owing into the appliance and free blowing out!
• Fit the fan in such a way that access to the fan for the purpose of maintenance work is always
guaranteed and the fan can be dismantled without disproportionate efforts being necessary.
• Ensure sufcient free space in the vicinity of the fan in order to be able to carry out any necessary
maintenance work.
• Fit the fan in the correct direction of air ow (in accordance with the arrow on the device).
• Fit the fan with B3 motors and with „air direction S“ in such a way that the mounting feets of the
electric motor are horizontal below the motor.
To avoid vibration transmissions to the channel system, installation of compensators with the corresponding
registrations (if necessary) is recommended.
In order to avoid vibration transmissions to surrounding components, installation of vibration dampers and
canvas supports is recommended.
NOTE Risk of damage to the fan.
Spring vibration mounts of unsuited materials do not full their function!
For smoke exhaust fans (B), (K) and (F) only use spring vibration mounts made of steel,
e.g. Systemair FSD or ZSD.
44
Axial, smoke and heat exhaust fans, series AX