IMO AXC 2014 04
Type Constructional peculiarities
AXC
As a default, the fans are provided in protection class IP55, ISO F. The fan can be run in per-
manent operation at 55 °C ambient and conveying temperature, in the ISO H version, it can
be run at up to 100 °C, depending on the nish.
AXC-D
Fans are designed as roof fans. Assembly on the roof is via a base plate. In order to stop
water entering, a blowing hood is arranged on the pressure side with a bird-protection grid.
Snowload class 0.
AXC-P Fan has been provided with a base plate. Assembly is on a wall.
AXC-G
Fans constructed as garage version. Arrangement of two fans in series, switched behind one
another
AXR
Impeller reversible. In reversing operation, approximated 100 % of the air output will be
achieved. According to the installation location.
AXC(B),
AXC(K),
AXR(B),
AXR(K)
Three phase motors (400 V, 50 Hz, type B3) without thermal protection, protection class:
IP54, ISO H.
The fan can be run both in permanent operation at 55 °C ambient temperature and also
(once) for 120 min at 300 °C conveying temperature. Certied to EN12101-3 TU Munich,
CE certicate, see annex. Temperature resistant terminal box. The connection wire from the
motor to the terminal box is protected via an additional exible metal hose. Standard motors
without motor protection.
AXC(F),
AXR(F)
Three phase motors (400 V, 50 Hz, type B30) without thermal protection, protection class:
IP55, ISO H.
The fan can be run both in permanent operation at 55 °C ambient temperature and also
(once) for 120 min at 300 °C conveying temperature. Certied to EN12101-3, CE certicate,
see annex. Temperature resistant terminal box. The connection wire from the motor to the
terminal box is protected via an additional exible metal hose. Standard motors without mo-
tor protection.
AXCBF
Directly powered axial fan with motor outside the air ow. 400 V, 50 Hz in IP55 ISO F. Stan-
dard conveying direction „D“, pressing across motor. The fan can be run in permanent operati-
on up to 200 °C conveying temperature. Maximum ambient temperature until 55°C. Housing
anges on both sides with bores according to eurovent 1/2 standard.
B3 conventional motors with add-on terminal box.
Constructional peculiarities of the types of fan
The axial fans have been developed as a standard for horizontal, standing assembly on vibration dampers.
Suction across motor – air direction „S“.
Following prior design, the fans can also be intended for vertical use –
air direction „SO“ or „SU“ (see illustrations).
S SU SO
40
Axial, smoke and heat exhaust fans, series AX