IMO AXC 2014 04

6 Safety devices
The motors have been provided with thermal protection via resistors (PTC) as a standard.
Provision with thermocontacts is possible if required by the customer.
The smoke exhaust versions (B) and (F) are provided without any thermal protection.
7 Constructional set-up
These fans are directly powered axial fans, in which the motor is positioned directly in the air ow.
The main air direction is suctioned across the motor.
The outside of the fans is formed by a tubular housing of galvanized steel sheet, which has a ange with
bores according to eurovent 1/2 standard pressed on both sides.
The axial impeller comprises an aluminium cast alloy and have proled blades and an efcient hub ratio.
Directly powered axial fans are arranged with the motor inside the air ow.
In B3 conventional motors, the motorbearing console is of galvanized steel sheet. In B30 pad mounted mo-
tors, the motor is tted on the housing via threaded rods or a welded motor support.
As a default, the fans are provided with three phase motors (400 V, 50 Hz) with integrated resistor. The elec-
trical motor protection class is at least IP 54, ISO F.
The fans can be run in permanent operation from –20 °C to 55 °C ambient and conveying temperature.
The hub construction permits innite adjustment of the blade angle at a standstill. The dynamic counterbalan-
cing is done according to ISO 1940 T1, Class G 6.3.
The electrical connection is via a terminal box positioned on the outside of the housing, the motor connec-
tions are carried out in the factory.
The standard motors of the axial fans are suited for operation with a frequency inverter.
If the fans are controlled with a frequency inverter, connection of the thermal protection, resistor (standard
PTC) or also thermocontacts (TC) in the motor is necessary.
39
AX - 01.2013