IMO AXC 2014 04

Type Differing uses
AXC-B Ventilator mounted in 20 mm isolated casing
AXC-D
The „D“ series of axial fans is designed as a roof fan with a base plate and with roof cowl.
Assembly on the roof.
AXC-P Fan has been provided with a tting plate. Assembly on the wall
AXC-G
In the „G series, two fans are arranged behind one another. If one of the fans fails and the
second fan continues to run, this specic arrangement ensures that at least 66 % of the total
air volume ow originally planned can continue to be conveyed. This is necessary, amongst
other things, in the use of the fans for removal of CO or also smoke extraction from garages.
AXC(B),
AXC(K),
AXR(B),
AXR (K)
The smoke exhaust fans can also be used for CO removal. The temperature resistance of the
smoke exhaust fans for the event of smoke removal can be seen from the name plate (300
°C/120 min). Version (B) is suited for exhaust of re gases, temperature classication pursu-
ant to DIN EN 12101 part 3 for at least one time 300 °C for 120 minutes. This series of fans
can be also be used for daily ventilation as required, thus fullling a double function.These
fans will be provided any without thermal protection.
AXC(F),
AXR(F)
The smoke exhaust fans can also be used for CO removal. The temperature resistance of the
smoke exhaust fans for the event of smoke removal can be seen from the name plate (400
°C/120 min). Version (F) is suited for exhaust of re gases, temperature classication pursu-
ant to DIN EN 12101 part 3 for at least one time 400 °C for 120 minutes. This series of fans
can be also be used for daily ventilation as required, thus fullling a double function.These
fans will be provided any without thermal protection.
AXR The direction of conveying can be reversed by switching over the direction of rotation.
AXCBF
The AXCBF series is suited as a standard for any temperature of no more than 200 °C.
With speed control, the maximum admissible conveying temperature is 55 °C.
The conveying temperature without regulation may not exceed 200 °C or fall
below –20 °C.
Differing use of the types of fan
Any deviating use of the fans is deemed improper.
No liability is assumed for any personal and/or property damage resulting from this.
4 Personnel
4.1 Qualication
The electrical connections of the fans may only be carried out by trained electricians.
4.2 Personal protective equipment
Protective working gloves, protective working shoes and goggles for assembly, installation, maintenance and
control work are part of the personal protective equipment for assembly, maintenance and repair personnel.
37
AX - 01.2013
Axial, smoke and heat exhaust fans, series AX