IMO AXC 2014 04
Motor protection
Type
Motor
protection
Thermal protection,
standard
Speed regulation
AXC, -B, -D, -G, -P by customer PTC possible via frequency inverter.
AXC (B), (F), (K)
AXR (B), (F), (K)
without
without
(PTC optional)
possible via frequency inverter, needs to be
bridged in case of re
AXR by customer PTC possible via frequency inverter
AXCBF by customer PTC possible via frequency inverter
3 Proper use
The axial fans of the series AXC/AXR/AXCBF in the versions B, D, G, P, (K), (B) are intended for
installation in ventilation systems!
The axial fans of the series AXC/AXR/AXCBF in the versions B, D, G and P are ready-to-use products and are
used as components for ventilation appliances, machines and systems. With these fans, air can be sucked out,
inserted or also conveyed. As a standard, the fans are supplied with a thermal motor protection (PTC).
The fans can be installed both in channel systems and also with free suction via an admission nozzle and a
suction-side contact protection grid. Free blow-out via a contact protection grid is also possible following prior
consideration during design.
The axial fans may not be used in areas in which an explosion-capable atmosphere can be found. The fans are
not suited for suction of dusty or aggressive media or media with such a content of dust that operation of the
fan could be impaired by accumulation on the blades and on the fan housing.
• The maximum admissible operating data on the name plate apply to an air density ρ =1.2 kg/m³
(See level)and a maximum air humidity of 80 %. The fans are suited for an ambient temperature of
no more than 55 °C (pay attention to information on name plate). The temperature of the material
conveyed may not exceed 55 °C or fall below –20 °C.
• The maximum admissible temperatures stated above can be increased to an ambient temperature of
60 °C, 80 °C or even up to 100 °C (pay attention to precise information on name plate) by use of ISO H
motors. The temperature of the material conveyed may then not exceed 100 °C or fall below –20 °C.
• With the use of specic motors (pay attention to precise information on name plate), the fans can also be
used up to a maximum air humidity of 95 %.
• The motors cannot be voltage-controlled. Speed regulation is only possible via a customary frequency
inverter, e.g. Systemair FRQ or FXDM.
36