2.3 Types of fans
AXC …......... Axial fan up to a max. long-term temperature of 55°C
AXC…..…(B) Smoke exhaust axial fan, F300, EN12101-3 (300 °C/120 min)
AXC……..(F) Smoke exhaust axial fan, F400, EN12101-3 (400 °C/120 min)
AXC........(K) Smoke exhaust axial fan, F250, EN12101-3 (250 °C/120 min.)
AXR …......... Fan with truly reversible impeller
AXR……..(B) Reversible smoke exhaust axial fan, F300, EN12101-3 (300 °C/120 min)
AXR……. (F) Reversible smoke exhaust axial fan, F400, EN12101-3 (400 °C/120 min)
AXR........(K) Reversible smoke exhaust axial fan, F250, EN12101-3 (250 °C/120 min)
AXCBF ……. Thermo fan with encapsulated motor, permanent operation temp. up to a max. of 200 °C
Possible combinations:
AXC….-D Axial fan, roof mounting version with roof cowl and base frame
AXC….-P Axial fan, wall mounting version
AXC….-B Axial fan, inside a sound-insulated box
AXC….-G Axial fan, 2 fans connected in series (2-stage)
AXC….-G-B Axial fan, 2 fans connected in series (2-stage) inside a sound-isolated box
AXC…(B)-D Smoke exhaust axial fan, roof mounting version with roof cowl and base frame
AXC…(B)-P Smoke exhaust axial fan, wall mounting version
AXC…(B)-B Smoke exhaust axial fan in sound-isolated box
AXC…(B)-G Smoke exhaust axial fan, 2 fans connected in series (2-stage)
AXC..(B)-G-B Smoke exhaust axial fan, 2 fans connected in series (2-stage) inside a
sound-isolated box
AXC…(F)-B Smoke exhaust axial fan in sound-isolated box
AXC…(F)-G Smoke exhaust axial fan, 2 fans connected in series (2-stage)
AXC..(F)-G-B Smoke exhaust axial fan, 2 fans connected in series (2-stage) inside a
sound-isolated box
2.4 Data of the fans
2.5 Data of the motor
All the necessary data can be obtained from the operating instructions from the manufacturer of the motor.
2.6 Electrical connection
All the necessary data can be seen from the name plate in question or from the enclosed data sheet.Admis-
sible voltage tolerances according to IEC38: maximum +6 % or –10 % The measured curren may only exceed
the nominal current at nominal voltage by a maximum of 5 %. The wiring scheme and the manufacturer‘s
declaration from the manufacturer of the motor have been enclosed with the documentation.
Weight See data sheet
Protection class See data sheet
Voltage/current intensity See data sheet
Sound pressure level See data sheet
Admissible ambient temperature See data sheet
Admissible temperature for conveying See data sheet
Nominal diameter See data sheet
35
AX - 01.2013