DOP AXCP(B) AXCPV(B)005

Declaration of Performance
3 (4)AXC (B)-P, AXC (B)-PV / F300 (120)/315–1250 mm_005
ANNEX 1 / Complementary information on Installation / Application (EN 12101–3:2015 / Table F.8)
Mechanically driven exhaust appliances for smoke and heat control fans
Classification
Class Temperature [°C] Time [min]
[X]
F
200
200 120
[X]
F
300
300 60
[ ]
F
400
400 120
[ ]
F
400
400 90
[ ]
F
600
600 60
[ ]
F
842
-
Free Classification for information only
[X]
F
300
300 120
1) Location of the fan and insulation if so
[X] outside the building without thermal insulation
[X] outside the building including thermal insulation
[X] inside the building but outside of the smoke reservoir without thermal insulation
[X] inside the building but outside of the smoke reservoir including thermal insulation
[X] inside the smoke reservoir
2) Installation
The specifications in the fan`s manual regarding permissible installation positions of the fan have to be considered.
[X] horizontal motor shaft, floor standing
[X] horizontal motor shaft, wall mounted
[X] horizontal motor shaft, suspended from ceiling
[X] vertical motor shaft, impeller below the motor
[X] vertical motor shaft, impeller above the motor
[X] vertical motor shaft, mounted onto the face of wall
[X] vertical motor shaft, suspended from ceiling
Mechanically driven exhaust appliances for smoke and heat control fans
3) Flexible connections tested with the fan
[X] flexible connection inlet side
[X] flexible connection outlet side
[X] flexible connection inlet and outlet side
[ ] flexible connection cooling air connection
4) Cooling air
[ ] c
Air,q
Volumetric flow cooling air Air = min. volumetric flow q = max. cooling air temperature
6) Snow load
[ ] SL0 without deflector
[ ]
SL125
[ ]
SL250
[ ]
SL500
Systemair·GmbH,·Seehöfer·Straße·45,·97944·Boxberg,·Germany
Phone: +49 (0) 7930 9272 0 Fax: +49 (0) 7930 9272 92 -en_GB-