SYSHRW – Installation Operation Manual (IOM HRW 03 N 13GB)
Table Of Contents
- CONTENTS
- 1. GENERAL RECOMMENDATIONS
- 2. INSPECTION AND STORAGE
- 3. Generalities
- 4. Contents of parcel
- 5. Dimensions
- 6. handling
- 7. REFRIGERATION SPECIFICATIONS
- 8. TECHNICAL SPECIFICATIONS
- 9. ELECTRIC SPECIFICATIONS
- 10. INSTALLATION
- 11. DUCTING AND NOISE LEVEL REDUCTION
- 12. HYDRAULIC CONNECTIONS
- 13. WIRiNG DIAGRAM AND LEGEND
- 14. ELECTRICAL CONNECTIONS
- 15. RCX and µbms control modules wiring
- 15.1. WALL MOUNTING
- 15.2. ELECTRICAL CONNECTIONS
- 15.3. APPLIANCE configuration
- 15.4. Return air temperature measurement
- 15.5. POWER FAILURE
- 15.6. REMOTE ON/OFF make/break SWITCH
- 15.7. RCX ONLY
- 15.8. µBMS SUPERVISION MODULE
- 15.9. MODBUS
- 15.10. ADDRESSING Procedure
- 15.11. µBMS SUPERVISION MODULE
- 15.12. MOTORISED WATER VALVE
- 16. FINAL TASKS
- 17. STARTING - RECOMMENDATIONS - SETTINGS
- 18. MAINTENANCE and servicing
- 18.1. FAN DRIVE SYSTEMS
- 18.2. FAULT FINDING
- 18.2.1. NeIther the fan noR the COMPRESSoR operate
- 18.2.2. ventilation (FAN) mode operates but the compressor does not operate
- 18.2.3. INSUFFICIENT COOLING OR HEATING Production
- 18.2.4. INSUFFICIENT WATER FLOW AT THE LEVEL OF THE PLATE EXCHANGER.
- 18.2.5. appearance OF WATER DROPLETS IN THE appliance
- 18.2.6. AppEARANCE OF ABNORMAL NOISES AND vibrationS IN THE CASING
- 18.3. ALARM CODES
- 19. In-Warranty Return Material Procedure
- 20. Service and Spare Parts Order
- WIRING DIAGRAM
- SCHEMAS ELECTRIQUES
- STROMLAUFPLANS
- SCHEMA ELETRICO
- ESQUEMA ELECTRICO
English
34 SysHrw
18.3.3. HEATING MODE
(**) This case only concerns installations where the valve is tted on the water loop upstream of the
machine.
(***) Lockout if 3 faults within 1 hour. Cut the mains power supply for 5 seconds, and then reconnect.
Example: 111 000 000
² 1 corresponds to one ash of the LED situated on the STORM2 circuit board.
² 0 indicates that there is no ash.
In this precise case, there will be 3 ashes, then the ashing will stop for a while (a few seconds), then there
will be 3 further ashes and so on until the fault is cancelled. Then the LED is off in OFF mode, and xed on
in ON mode.
FAULT LED LARM CODE POSSIBLE CAUSE CORRECTIVE ACTION
ACTION FOR CANCELLING FAULT CODE
AFTER CORRECTION
High pressure or
water ow fault
100000000
1 flashe
Insufficient airflow Check proper fan operation.
Cut the mains power supply for
5 seconds, and then reconnect.
Clogged filters. Clean or replace the filters.
Too high aeraulic pressure loss due to an
obstruction in the intake duct.
Test the aeraulic network.
Insufficient water flow or no water flow at
the level of the appliance.
Test the flow from the pump on the main loop.
Stop cock or water inlet valve shut (**)
Test the valve electrical supply. Test the direction of
flow. Open the valve.
Faulty pressure differential Check electrical connections.
Pressostat defective, broken wire or short
circuit.
Check the proper connection of the HP pressostat and/or
conduct a continuity test.
Low pressure
110000000
2 flashes
Insufficient water flow in the appliance. Test the pump flow at the level of the main loop.
The fault code is automatically
cancelled after correction(***).
The LED stops flashing and the green
light remains on.
Pressostat sensor defective, broken wire
or short circuit.
Check the proper connection of the LP pressostat and/or
conduct a continuity test.
Refrigerant leak. Find and repair any leaks on the pipe circuits.
Water inlet valve closed (**)
Test the valve electrical supply. Test the direction of
flow.
Low water
temperature limit
111110000
5 flashes
Hot water loop temperature < 13°C . Test the temperature at the level of the main loop.
The fault code is automatically
cancelled after correction(***).
The LED stops flashing and the green
light remains on.
Insufficient water flow. Test the water flow at the level of the main loop.
High water
temperature limit
111111000
6 flashes
Hot water loop temperature > 35°C Test the temperature at the level of the main loop.
The fault code is automatically
cancelled after correction(***).
The LED stops flashing and the green
light remains on.
Insufficient water flow. Test the water flow at the level of the main loop.
Note: More than 2 alarm codes can be activated at the same time. Only the last code detected will be
visible on the STORM2 circuit board. After the source of the rst alarm code is resolved, the second code
will appear, and so on until all the faults are cancelled and until the LED stops ashing.