SYSHRW – Installation Operation Manual (IOM HRW 03 N 13GB)

Table Of Contents
English
19SysHrw
VERY IMPORTANT:
3N~400V-50HZ
The outdoor unit is equipped as standard with a phase sequence and cut-out controller located in the
electrical box.
THIS PRODUCT IS EQUIPPED WITH A PHASE SEQUENCE CONTROLLER. THE LED’s INDICATE THE FOLLOWING
CONDITIONS:
Green LED = 1
Yellow LED =1
Low voltage supply
The compressor rotation
direction is correct
Green LED = 1
Yellow LED =0
Phase inversion or phase
absent (L1)
The compressor and the
fans do not start.
Green LED = 0
Yellow LED =0
Phase absent (L2 or L3)
the compressor and the
fans do not start.
13.2.5. SETTING OF THERMAL PROTECTION AND FUSES
MODELS thermal relay
FT3
Magneto-thermal
trip switch
FF7
FF2 Fuse
/gG type
400V
096
2.6 A 2 A 25 A gG
120
3.4 A 2 A 32 A gG
14. ELECTRICAL CONNECTIONS
14.1. GENERALITIES
Ensure that the available electrical power supply and the network frequency are matched to the required
operating current, taking account of the appliances specic location and the current required to supply any
other appliances connected to the same circuit.
1. Ensure that the unit is supplied with the specied voltage. Two stufng boxes and one grommet hole
are provided on the side of the appliance. They are used respectively for the power and the control
wiring. The power supply line must be properly dimensioned with a motor supply type fuse or a
mains circuit breaker to protect the circuit against voltage surges. (Refer to the Makers Plate for the
voltages to be taken into consideration).
2. The electrical power supply three-phase 400V/3ph/50Hz must comprise a neutral to feed the control
circuit.
3. Always shut down the power supply to the unit before connecting the thermostat wiring.