SYSHRW – Installation Operation Manual (IOM HRW 01 N 21GB)
Table Of Contents
- CONTENTS
- 1. GENERAL RECOMMENDATIONS
- 2. INSPECTION AND STORAGE
- 3. Generalities
- 4. Contents of parcel
- 5. Dimensions
- 6. handling
- 7. REFRIGERATION SPECIFICATIONS
- 8. TECHNICAL SPECIFICATIONS
- 9. ELECTRIC SPECIFICATIONS
- 10. INSTALLATION
- 11. DUCTING AND NOISE LEVEL REDUCTION
- 12. HYDRAULIC CONNECTIONS
- 13. WIRiNG DIAGRAM AND LEGEND
- 14. ELECTRICAL CONNECTIONS
- 15. RCX and µbms REMOTE control wiring
- 15.1. WALL MOUNTING
- 15.2. ELECTRICAL CONNECTIONS
- 15.3. APPLIANCE configuration
- 15.4. Return air temperature measurement
- 15.5. POWER FAILURE
- 15.6. REMOTE ON/OFF make/break SWITCH
- 15.7. RCX ONLY
- 15.8. µBMS SUPERVISION MODULE
- 15.9. MODBUS
- 15.10. ADDRESSING Procedure
- 15.11. µBMS SUPERVISION MODULE
- 15.12. MOTORISED WATER VALVE
- 16. FINAL TASKS
- 17. STARTING - RECOMMENDATIONS - SETTINGS
- 18. MAINTENANCE and servicing
- 18.1. FAULT FINDING
- 18.1.1. NeIther the fan noR the COMPRESSoR operate
- 18.1.2. ventilation (FAN) mode operates but the compressor does not operate
- 18.1.3. INSUFFICIENT COOLING OR HEATING Production
- 18.1.4. INSUFFICIENT WATER FLOW AT THE LEVEL OF THE PLATE EXCHANGER.
- 18.1.5. appearance OF WATER DROPLETS IN THE appliance
- 18.1.6. AppEARANCE OF ABNORMAL NOISES AND vibrationS IN THE CASING
- 18.2. ALARM CODES
- 18.1. FAULT FINDING
- 19. In-Warranty Return Material Procedure
- 20. Service and Spare Parts Order
- WIRING DIAGRAM
- SCHEMAS ELECTRIQUES
- STROMLAUFPLANS
- SCHEMA ELETRICO
- ESQUEMA ELECTRICO
English
This equipment contains uorinated gas with greenhouse gas effects covered by the Kyoto
agreement.
Caution
SYSHRW units use the R407C uoro-carbonated uid, belonging to group 2 as dened in directive
2014/68/UE. Considering the maximum operating pressure of these units (42 bar g), they integrate
category 2 (or lower) components as dened in directive 2014/68/UE.
Caution
Non-compliance with one of these obligations constitutes an offense and can result in nancial
penalties.
Furthermore, compliance of the equipment with the uorinated gases regulation must be proven to
the insurance company.
Caution
7SYSHRW
7. REFRIGERATION SPECIFICATIONS
7.1. REFRIGERANT CHARGE
The type and quantity of refrigerating uid per circuit are indicated on the product plate.
The installer and end user will get informed on local environmental regulations for the installation, operation
and disposal of the equipment ; more particularly, for the collection of substances hazardous for the
environment (refrigerating uid, oil, antifreeze, etc.). A refrigerating uid, whatever it is, must not be vented.
Refrigerating uids must be handled by skilled personnel.
7.2. FLUOROCARBON GAS REGULATIONS
The EC No. 517/2014 regulation covering uorinated greenhouse gases requires of refrigeration equipment
operators to comply with the following ve obligations:
Greenhouse gas quantity (kg of CO
2
) = Quantity of gas (kg) x gas' GWP
Quantity of greenhouse gas expressed in weight
(kg) and CO
2
equivalent
Quantity of gas: amount of gas contained in the
machine in kg (see ID plate)
GWP (Global Warming Potential) of the gas contained
in the machine (see ID plate)
² GWP for the R410A = 2088
² GWP for the R407C = 1774
7.2.1. CALCULATING GREENHOUSE GAS QUANTITIES
1. Installation, servicing, maintenance as well as checking the sealing must be carried out by qualied
personnel.
2. The uorinated gas must be recovered during servicing and maintenance as well as the end of the
installation.
3. All the necessary measures must be taken to prevent the leakage of uorinated gases and any leaks
must be repaired as rapidly as possible.
4. Regular checks on any leaks must be performed according to the following conditions:
for equipment containing uorinated greenhouse gases in quantities greater than or equal to
the equivalent of 5 tonnes of CO
2
but less than the equivalent of 50 tonnes of CO
2
:
at least every twelve months or, if a leak detection system is installed, at least every twenty-
four months
for equipment containing uorinated greenhouse gases in quantities greater than or equal to
the equivalent of 50 tonnes of CO
2
but less than the equivalent of 500 tonnes of CO
2
:
at least every six months or, if a leak detection system is installed, at least every twelve
months
for equipment containing uorinated greenhouse gases in quantities greater than or equal to
the equivalent of 500 tonnes of CO
2
:
at least every three months or, if a leak detection system is installed, at least every six
months.
5. A document grouping a description of all the operations carried out on the cooling circuit must be
drafted and conserved.