SYSHRW – Installation Operation Manual (IOM HRW 01 N 21GB)
Table Of Contents
- CONTENTS
- 1. GENERAL RECOMMENDATIONS
- 2. INSPECTION AND STORAGE
- 3. Generalities
- 4. Contents of parcel
- 5. Dimensions
- 6. handling
- 7. REFRIGERATION SPECIFICATIONS
- 8. TECHNICAL SPECIFICATIONS
- 9. ELECTRIC SPECIFICATIONS
- 10. INSTALLATION
- 11. DUCTING AND NOISE LEVEL REDUCTION
- 12. HYDRAULIC CONNECTIONS
- 13. WIRiNG DIAGRAM AND LEGEND
- 14. ELECTRICAL CONNECTIONS
- 15. RCX and µbms REMOTE control wiring
- 15.1. WALL MOUNTING
- 15.2. ELECTRICAL CONNECTIONS
- 15.3. APPLIANCE configuration
- 15.4. Return air temperature measurement
- 15.5. POWER FAILURE
- 15.6. REMOTE ON/OFF make/break SWITCH
- 15.7. RCX ONLY
- 15.8. µBMS SUPERVISION MODULE
- 15.9. MODBUS
- 15.10. ADDRESSING Procedure
- 15.11. µBMS SUPERVISION MODULE
- 15.12. MOTORISED WATER VALVE
- 16. FINAL TASKS
- 17. STARTING - RECOMMENDATIONS - SETTINGS
- 18. MAINTENANCE and servicing
- 18.1. FAULT FINDING
- 18.1.1. NeIther the fan noR the COMPRESSoR operate
- 18.1.2. ventilation (FAN) mode operates but the compressor does not operate
- 18.1.3. INSUFFICIENT COOLING OR HEATING Production
- 18.1.4. INSUFFICIENT WATER FLOW AT THE LEVEL OF THE PLATE EXCHANGER.
- 18.1.5. appearance OF WATER DROPLETS IN THE appliance
- 18.1.6. AppEARANCE OF ABNORMAL NOISES AND vibrationS IN THE CASING
- 18.2. ALARM CODES
- 18.1. FAULT FINDING
- 19. In-Warranty Return Material Procedure
- 20. Service and Spare Parts Order
- WIRING DIAGRAM
- SCHEMAS ELECTRIQUES
- STROMLAUFPLANS
- SCHEMA ELETRICO
- ESQUEMA ELECTRICO
English
The Modbus interface, used to communicate with a GTC, is available as an option, factory
assembled or with a kit.
Caution
The use of the µBMS recall command is not compatible with the modbus communication. The
same terminals and addressing DIPs are used in both connection cases.
Caution
Shielded twisted pair wire must be used for interconnecting wiring. Wire impedance must be
between 100 and 130 Ohms and the wire surface section must be between 0.12 and 0.5 mm² (26
to 20 AWG). Larger wire may be used, but in this case connection to the terminal blocks can cause
problems.
Caution
MODBUS
RS 485
1 2 43
RS 485
12V GND
A- B+
- +
1 2 43
RS 485
12V GND
A- B+
1 2 43
RS 485
12V GND
A- B+
100m MAXI
30m MAXI
RCX
RS 485
12V
GND
A B
RCX
RS 485
12V
GND
A B
SYSHRW 1 SYSHRW 2 SYSHRW 3
28 SYSHRW
The MODBUS supervision can be connected to a maximum of 123 appliances.
² The maximum distance between the RCX and the rst unit is 30 metres.
² The maximum distance between the RCX and the furthest unit is 100 metres.
Note : When MODBUS supervision is used, all the units must have a unique address (see "Addressing
procedure").
123 SYSHRW
MAXIMUM
15.9. MODBUS