SYSHRW – Installation Operation Manual (IOM HRW 01 N 21GB)

Table Of Contents
English
25SYSHRW
15.3. APPLIANCE CONFIGURATION
15.3.1. FACTORY CONFIGURATION
Type J1 J2 Description
SYSHRW.H
OFF OFF Cooling and thermodynamic Heating
SYSHRW.H
with
heating
OFF ON
Thermodynamic Cooling + thermodynamic Heating or electric heating
depending on appliance return water temperature
SYSHRW.L
ON OFF Cooling only
SYSHRW.L
with
heating
ON ON Cool + heat by electric heat
15.3.2. CLIENT SETTINGS
DIP Switch Conguration
J6
OFF Normal mode
ON
Forced mode dry contact (remote ON/OFF)
DIP Switch Conguration
J3
OFF the fan is controlled via the compressor and the ICT sensor in Heating mode.
ON
the fan operates continuously in Heating mode, except in OFF mode.
J4
OFF No anti-stratification mode
ON
Anti-stratification mode active. Fan cycling
J5
OFF ambient temperature is measured at the RCX.
ON
ambient temperature is measured with the Return sensor (RT) located on the appliance.