SYSHRW – Installation Operation Manual (IOM HRW 01 N 21GB)
Table Of Contents
- CONTENTS
- 1. GENERAL RECOMMENDATIONS
- 2. INSPECTION AND STORAGE
- 3. Generalities
- 4. Contents of parcel
- 5. Dimensions
- 6. handling
- 7. REFRIGERATION SPECIFICATIONS
- 8. TECHNICAL SPECIFICATIONS
- 9. ELECTRIC SPECIFICATIONS
- 10. INSTALLATION
- 11. DUCTING AND NOISE LEVEL REDUCTION
- 12. HYDRAULIC CONNECTIONS
- 13. WIRiNG DIAGRAM AND LEGEND
- 14. ELECTRICAL CONNECTIONS
- 15. RCX and µbms REMOTE control wiring
- 15.1. WALL MOUNTING
- 15.2. ELECTRICAL CONNECTIONS
- 15.3. APPLIANCE configuration
- 15.4. Return air temperature measurement
- 15.5. POWER FAILURE
- 15.6. REMOTE ON/OFF make/break SWITCH
- 15.7. RCX ONLY
- 15.8. µBMS SUPERVISION MODULE
- 15.9. MODBUS
- 15.10. ADDRESSING Procedure
- 15.11. µBMS SUPERVISION MODULE
- 15.12. MOTORISED WATER VALVE
- 16. FINAL TASKS
- 17. STARTING - RECOMMENDATIONS - SETTINGS
- 18. MAINTENANCE and servicing
- 18.1. FAULT FINDING
- 18.1.1. NeIther the fan noR the COMPRESSoR operate
- 18.1.2. ventilation (FAN) mode operates but the compressor does not operate
- 18.1.3. INSUFFICIENT COOLING OR HEATING Production
- 18.1.4. INSUFFICIENT WATER FLOW AT THE LEVEL OF THE PLATE EXCHANGER.
- 18.1.5. appearance OF WATER DROPLETS IN THE appliance
- 18.1.6. AppEARANCE OF ABNORMAL NOISES AND vibrationS IN THE CASING
- 18.2. ALARM CODES
- 18.1. FAULT FINDING
- 19. In-Warranty Return Material Procedure
- 20. Service and Spare Parts Order
- WIRING DIAGRAM
- SCHEMAS ELECTRIQUES
- STROMLAUFPLANS
- SCHEMA ELETRICO
- ESQUEMA ELECTRICO
English
25SYSHRW
15.3. APPLIANCE CONFIGURATION
15.3.1. FACTORY CONFIGURATION
Type J1 J2 Description
SYSHRW.H
OFF OFF Cooling and thermodynamic Heating
SYSHRW.H
with
heating
OFF ON
Thermodynamic Cooling + thermodynamic Heating or electric heating
depending on appliance return water temperature
SYSHRW.L
ON OFF Cooling only
SYSHRW.L
with
heating
ON ON Cool + heat by electric heat
15.3.2. CLIENT SETTINGS
DIP Switch Conguration
J6
OFF Normal mode
ON
Forced mode dry contact (remote ON/OFF)
DIP Switch Conguration
J3
OFF the fan is controlled via the compressor and the ICT sensor in Heating mode.
ON
the fan operates continuously in Heating mode, except in OFF mode.
J4
OFF No anti-stratification mode
ON
Anti-stratification mode active. Fan cycling
J5
OFF ambient temperature is measured at the RCX.
ON
ambient temperature is measured with the Return sensor (RT) located on the appliance.