SYSHRW Engineering Data Manual (EDM HRW S 4GB)

µBMS mini-supervision station
SYSHRW
4
Control Features (continued)
Variable sequential start-up function : when the system is rst
energised, or after a power cut, or after opening and closing the "CLK"
contact, a random time delay of 0 to 30 seconds is introduced by the
electronic board to prevent the water source heat pumps from all
starting up simultaneously, thus avoiding a power surge.
Emergency shut-down / stand-by / night setback : the electronic
board has two "CLK" terminals which shut the unit down immediately.
By incorporating an area thermostat in series, the "CLK" contact can
also be used as a night setback and the water source heat pump will
start up again as soon as the ambient temperature drops below the
set point of the setback thermostat.
Anti-freeze safety function : this is provided by two temperature
sensors. In cooling mode an "ICT" temperature sensor located in the
nned coil protects the water source heat pump against accidental
freezing.
In heating mode, the safety function is provided by an "LWT" minimum
water outlet temperature sensor.
A minimum water ow in the unit is ensured by a differential pressure
switch.
The automatic reset LP pressure switch completes the anti-freeze
safety function by monitoring a minimum acceptable suction pressure
to ensure correct operation of the compressor.
High temperature safety function : the "ICT & LWT" temperature
sensors check that the condensation temperature at the nned coil
and the water temperature at the outlet of the water/refrigerant heat
exchanger do not exceed the authorised limits.
The manual reset HP pressure switch completes the high temperature
safety function.
Condensate drain pan uid level safety function : the STORM 2
electronic board permanently monitors the water level in the
condensate drain pan, by means of a oat type contact switch.
If the water reaches an abnormally high level, the machine is switched
to safety mode.
The STORM 2 electronic board also enables the general machine fault
to be sent to a remote fault relay via a dry contact (optional).Phase
monitor : The water source heat pumps (three-phased models) are
factory equipped with a phase monitor to detect the presence and
order of the phases.
Motorized valve : The STORM 2 electronic board has a 230 volt output
for an (optional) motorized valve controlled by the operation of the
compressor, in order to enable the ow-rate of the hydraulic pump(s)
to be regulated according to the manometric pressure in the water
source.
System without water source heater : The STORM 2 electronic board
can be congured to stop the water source heat pump if the water
temperature in the system becomes too low, and to automatically start
an electric air ow heater which is monitored by the room temperature
regulation sensor (RCX) or the air intake temperature sensor (RAT).
Electric heater : SYSHRW water source heat pumps can be factory
equipped with an optional in-duct air heater located at the fan outlet.
The electric heaters are also available in kit.
The electric heater function can, depending on the conguration of
the STORM 2 electronic board, be used in place of the thermodynamic
heating as soon as the temperature in the water system drops below
a minimum limit, or it can be used as an electric heating system on
its own.
The SYSHRW size 019, which operate on a single-phase 230 volt
mains supply, is factory equipped with two electric heater stages. The
other models, which operate on a three-phase 400 volt mains supply,
have a single-stage electric heater.
µBMS mini-supervision station
This centralised control unit is proposed as an option, and can be
installed in place of the local RCX remote control or connected to the
STORM 2 electronic board as a supervision station to monitor and
manage 32 water source heat pumps in 15 zones from a single point,
in addition to the local RCX remote controls.
The µBMS mini-supervision station enables the zones to be
programmed with global control for all zones, or with individual control
of each zone with programming of the operating time ranges over
a 7 day period, with management of the heating, cooling and night
setback modes.
It also provides the possibility of having different set-points in different
zones.
MODBUS interface
The ModBus interface for communication with a BMS, is available as
optional in the STORM 2 electronic board.