IOM SYSCW AR R513A (IOM CWAR 02 N 1GB/12.21)
Table Of Contents
- CONTENTS
- 1. GENERAL RECOMMENDATIONS
- 2. INSPECTION AND STORAGE
- 3. WARRANTY
- 4. TECHNICAL SUPPORT AND AFTER-SALES SERVICE HOTLINE
- 5. PRESENTATION
- 6. CONTENTS OF PACKAGE
- 7. DIMENSIONS
- 8. HANDLING
- 9. TECHNICAL SPECIFICATIONS
- 10. INSTALLATION
- 11. UNCLAMPING THE COMPRESSOR
- 12. HYDRAULIC LINKS
- 13. WIRING DIAGRAM AND LEGEND
- 14. ELECTRICAL CONNECTIONS
- 15. REGULATION
- 16. FINAL TASKS
- 17. STARTING - RECOMMENDATIONS - SETTINGS
- 18. MAINTENANCE
- 18.1. MAINTENANCE PROCEDURES
- 18.2. FAULT FINDING
- 18.2.1. NEITHER THE FAN NOR THE COMPRESSOR OPERATE
- 18.2.2. VENTILATION (FAN) MODE OPERATES BUT THE COMPRESSOR DOES NOT OPERATE
- 18.2.3. INSUFFICIENT COOLING OR HEATING PRODUCTION
- 18.2.4. INSUFFICIENT WATER FLOW AT THE LEVEL OF THE COAXIAL EXCHANGER.
- 18.2.5. APPEARANCE OF WATER DROPLETS IN THE APPLIANCE
- 18.2.6. APPEARANCE OF ABNORMAL NOISES AND VIBRATIONS IN THE CASING
- 18.3. ALARM CODES
- 19. WARRANTY CLAIM - MATERIAL RETURN PROCEDURE
- 20. ORDERING SERVICE AND SPARE PARTS ORDER
- 21. DISPOSAL
- DIMENSIONS
- SYSCW-AR R513A VC BA
- SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA
- SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA
- SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA
- SYSCW-AR R513A VNL FA
- HYDRAULIC CONNECTIONS
- SYSCW-AR R513A VC BA / SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA / SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA / SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA / SYSCW-AR R513A VNL FA
- REFRIGERANT CIRCUIT DIAGRAM
- WIRING DIAGRAM
- DIMENSIONS
- SYSCW-AR R513A VC BA
- SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA
- SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA
- SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA
- SYSCW-AR R513A VNL FA
- RACCORDEMENT HYDRAULIQUE
- SYSCW-AR R513A VC BA / SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA / SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA / SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA / SYSCW-AR R513A VNL FA
- SCHEMA DU CIRCUIT FRIGORIFIQUE
- SCHEMAS ELECTRIQUES
- ABMESSUNGEN
- SYSCW-AR R513A VC BA
- SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA
- SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA
- SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA
- SYSCW-AR R513A VNL FA
- HYDRAULIKANSCHLÜSSE
- SYSCW-AR R513A VC BA / SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA / SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA / SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA / SYSCW-AR R513A VNL FA
- KÄLTEKREISLAUFDIAGRAMM
- STROMLAUFPLANS
- DIMENSIONI
- SYSCW-AR R513A VC BA
- SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA
- SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA
- SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA
- SYSCW-AR R513A VNL FA
- COLLEGAMENTI IDRAULICI
- SYSCW-AR R513A VC BA / SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA / SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA / SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA / SYSCW-AR R513A VNL FA
- SCHEMA DEL CIRCUITO REFRIGERANTE
- SCHEMA ELETRICO
- DIMENSIONES
- SYSCW-AR R513A VC BA
- SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA
- SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA
- SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA
- SYSCW-AR R513A VNL FA
- CONEXIONES HIDRÁULICAS
- SYSCW-AR R513A VC BA / SYSCW-AR R513A VN BA
- SYSCW-AR R513A VC FA / SYSCW-AR R513A VN FA
- SYSCW-AR R513A VCL BA / SYSCW-AR R513A VNL BA
- SYSCW-AR R513A VCL FA / SYSCW-AR R513A VNL FA
- ESQUEMA DEL CIRCUITO FRIGORIFÍCO
- ESQUEMA ELECTRICO
English
11SYSCW-AR R513A
9.5. REFRIGERATION SPECIFICATIONS
9.5.1. REFRIGERANT CIRCUIT DIAGRAM
SEE APPENDIX
9.5.2. REFRIGERANT CHARGE
The type and quantity of refrigerating uid per circuit are indicated on the product plate.
The installer and end user will get informed on local environmental regulations for the installation, operation
and disposal of the equipment ; more particularly, for the collection of substances hazardous for the
environment (refrigerating uid, oil, antifreeze, etc.). A refrigerating uid, whatever it is, must not be vented.
Refrigerating uids must be handled by skilled personnel.
9.5.3. FLUOROCARBON GAS REGULATIONS
The EC No. 517/2014 regulation covering uorinated greenhouse gases requires of refrigeration equipment
operators to comply with the following ve obligations:
Greenhouse gas quantity (kg of CO
2
) = Quantity of gas (kg) x gas' GWP
Quantity of greenhouse gas expressed in weight
(kg) and CO
2
equivalent
Quantity of gas: amount of gas contained in the
machine in kg (see ID plate)
GWP (Global Warming Potential) of the gas contained
in the machine (see ID plate)
² GWP for the R513A = 631
9.5.3.1. CALCULATING GREENHOUSE GAS QUANTITIES
1. Installation, servicing, maintenance as well as checking the sealing must be carried out by qualied
personnel.
2. The uorinated gas must be recovered during servicing and maintenance as well as the end of the
installation.
3. All the necessary measures must be taken to prevent the leakage of uorinated gases and any leaks
must be repaired as rapidly as possible.
4. Regular checks on any leaks must be performed according to the following conditions:
for equipment containing uorinated greenhouse gases in quantities greater than or equal to
the equivalent of 5 tonnes of CO
2
but less than the equivalent of 50 tonnes of CO
2
:
at least every twelve months or, if a leak detection system is installed, at least every twenty-
four months
for equipment containing uorinated greenhouse gases in quantities greater than or equal to
the equivalent of 50 tonnes of CO
2
but less than the equivalent of 500 tonnes of CO
2
:
at least every six months or, if a leak detection system is installed, at least every twelve
months
for equipment containing uorinated greenhouse gases in quantities greater than or equal to
the equivalent of 500 tonnes of CO
2
:
at least every three months or, if a leak detection system is installed, at least every six
months.
5. A document grouping a description of all the operations carried out on the cooling circuit must be
drafted and conserved.
This equipment contains uorinated gas with greenhouse gas effects covered by the Kyoto
agreement.
Caution
SYSCW-AR units use the R513A uoro-carbonated uid, belonging to group 2 as dened in directive
2014/68/UE. Considering the maximum operating pressure of these units (18 bar g), they integrate
category 2 (or lower) components as dened in directive 2014/68/UE.
Caution
Non-compliance with one of these obligations constitutes an offense and can result in nancial
penalties.
Furthermore, compliance of the equipment with the uorinated gases regulation must be proven to
the insurance company.
Caution