33
Air inlet temperature (°C db)
Water inlet temperature (°C)
10
15
20
25
30
35
40
45
50
32
14 15 16 17 18 19 20 21 22 23 24 25 26
27
Air inlet temperature (°C)
Water inlet temperature (°C)
14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
8 10 12
40
50
60
70
80
90
100
Max nominal water flow (%)
10 SYSCW-AR R513A
9.4. OPERATING LIMITS
9.4.1. TEMPERATURE LIMITS
9.4.2. FLOW LIMITS
Operation within the shaded ranges requires special attention to the minimum water ow rate.
Caution
Conditions in
accordance with the
standard: EN 14511-2
* Conditions in accordance with the standard: EN 14511-2
MODELS 07R 09R
PV - Minimum air ow m
3
/h
250 340
MV - Nominal air ow * m
3
/h
340 400
GV - Maximum air ow m
3
/h
400 460
MODELS
07R 09R
Nominal water ow l/h
351 405 434 586
50% Nominal water ow l/h
180* 203 217 293
Maximum hydraulic pressure bar
10 10