EDM SYSCW AR R513A (EDM CWAR 02 S 1GB/12.21)

15
20
25
30
35
40
45
50
23
20 21 22 23 24 25 26 27 28 29 30 31 32
33
Air inlet temperature (°C db)
Water inlet temperature (°C)
10
15
20
25
30
35
40
45
32
14 15 16 17 18 19 20 21 22 23 24 25 26
14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
52
8 10 12
40
50
60
70
80
90
100
110
Water inlet temperature (°C)
Max nominal water flow (%)
* Cutoff water ow: 180l/h
SYSCW-AR R513A
7
Operating Limits
Environment
This equipment is designed for an internal installation only.
In general, the sheltered locations, such as garages, attic, etc, do not provide sufcient protection against extreme temperatures and/or
humidity, and the performance, the reliability and the life span of the equipment can be decreased.
Temperature limits
Flow limits
* Conditions in accordance with the standard: EN 14511-2
MODELS 07 09
PV - Minimum air ow m
3
/h
250 340
MV - Nominal air ow * m
3
/h
340 400
GV - Maximum air ow m
3
/h
400 460
MODELS
07 09
Nominal water ow l/h
351 405 434 586
50% Nominal water ow l/h
180* 203 217 293
Maximum hydraulic pressure bar
10 10