Refrigerant R513-A SYSCW-AR R513 Water Source Heat Pumps - Vertical console Version Models 07R to 09R 1.8 to 2.6kW 1.7 to 2.
SYSCW-AR R513A Some advantages... RAL 9010 painted G2 filter is supplied as standard. Front or bottom access to the filter. 3-fan speeds Temperature range : 15 to 45 °C EC version is available as optional Front panel is very easy to remove in order to facilitate access to internal components. Direct external access Schrader valves (HP&LP) available for a pressure tap on the refrigerant circuit.
2 SYSCW-AR R513A Unit Description Generalities Q RAL 9010 painted cabinet with optimal compactness. Q High efficiency units with high COP values. Q Complete access to the compressor, fan and electrical box, through front removable panel. Q Q Q Condensate drain pan with anti-corrosion treatment by The water source outlet and return connectors are located on the outside of the unit in several configurable positions. They are of female gas threaded type (1/2").
SYSCW-AR R513A Versions SYSCW-AR R513A VC - filter assembly below (BA) SYSCW-AR R513A VC - front filter assembly (FA) SYSCW-AR R513A VCL - filter assembly below (BA) SYSCW-AR R513A VCL - front filter assembly (FA) SYSCW-AR R513A VN - filter assembly below (BA) SYSCW-AR R513A VN - front filter assembly (FA) SYSCW-AR R513A VNL - filter assembly below (BA) SYSCW-AR R513A VNL - front filter assembly (FA) 3
4 SYSCW-AR R513A Control Features All SYSCW-AR R513A water source heat pumps are, in their standard version, equipped with a Siemens electronic control RCS remote control A RCS remote control is supplied as optional (factory fitted or wall system which manages their operation and their safety devices. mounted). Anti-freeze safety function : this is provided by two temperature It enables individually controlled operation or stand-alone sensors.
SYSCW-AR R513A Models designation CW-AR07R . H . 1 2 REP. VN . 3 HB . ER . LN 4 5 6 . SYS 7 . EC 8 . BA . MBRT 9 10 . CB . 11 RCSM .
6 SYSCW-AR R513A Refrigerant Flow Diagram HP WATER R513A AIR LWT RV C1 E1 LP E2 FILTER LR1 Y1 RT IF CAP FS ICT C1 Compressor E2 Finned coil RT Air temperature sensor RV Cycle reversal valve IF Fan motor ICT Anti-freezing protection sensor E1 Plate heat exchanger Schrader valve LWT Outlet water temperature sensor LR1 Liquid reservoir HP High pressure switch FS Flow switch CAP Expansion device LP Low pressure switch Y1 Water circuit by-pass valve
SYSCW-AR R513A Operating Limits Environment This equipment is designed for an internal installation only. In general, the sheltered locations, such as garages, attic, etc, do not provide sufficient protection against extreme temperatures and/or humidity, and the performance, the reliability and the life span of the equipment can be decreased.
8 SYSCW-AR R513A Physical Data Models 07R PV 1618 1208 326 4.96 1801 436 4.13 MV 1690 1410 345 4.9 1790 395 4.53 GV 1700 1660 362 4.7 1793 385 4.66 09R PV 2001 1440 463 4.32 2638 640 4.12 MV 2040 1600 480 4.25 2630 610 4.31 GV 2051 1833 502 4.09 2632 597 4.41 5.99 400 20 5.13 340 15 5.99 400 20 7.28 460 28 355 3.84 180 410 5.2 205 425 5.6 213 578 10.5 289 434 5.84 217 586 10.8 293 439 5.97 220 593 11.1 297 51.5 42.5 36 54.3 45.
SYSCW-AR R513A Physical Data (continued) Models 07R PV 1618 1208 329 4.92 1801 439 4.11 MV 1690 1410 355 4.75 1790 405 4.41 GV 1700 1660 396 4.29 1793 419 4.28 09R PV 2001 1440 462 4.33 2 638 639 4.13 MV 2040 1600 487 4.19 2 630 617 4.26 GV 2051 1833 532 3.86 2 632 627 4.20 400 54 340 14 400 27 460 58 355 3.84 180 410 5.2 205 425 5.6 213 578 10.5 289 434 5.84 217 586 10.8 293 439 5.97 220 593 11.1 297 52 43 37 54.4 45.
SYSCW-AR R513A Air Flow Data MODEL SYSCW-AR 07 - EC MOTOR 140 Available pressure (Pa) 120 100 80 10V 9V 8V 60 7V 6V 40 5V 4V 3V 20 2V 0 0 100 200 LS 300 MS 400 500 HS 600 700 800 600 700 800 Air flow (m3/h) MODEL SYSCW-AR 09 - EC MOTOR 140 120 Available pressure (Pa) 10 100 80 10V 9V 8V 60 7V 6V 40 5V 4V 3V 20 2V 0 0 100 200 300 LS 400 MS HS 500 Air flow (m3/h)
SYSCW-AR R513A Acoustical Data SYSCW-AR 07 R513 LN Speeds Power level per octave band Lw dB 125 250 500 1 000 2 000 4 000 Lw dB(A) Lp global (1) NR (1) dB(A) LS 57.8 46.7 43.9 38.7 33.9 25.3 47.2 38.2 32 MS 58.0 51.1 47.0 42.8 38.2 28.2 49.8 40.8 34 HS 58.3 53.9 49.4 45.7 41.3 30.8 51.5 42.5 36 SYSCW-AR 07 R513 XLN Speeds Power level per octave band Lw dB 125 250 500 1 000 2 000 4 000 Lw dB(A) Lp global (1) NR (1) dB(A) LS 52.4 46.6 39.2 34.2 29.0 28.0 42.
SYSCW-AR R513A Dimensions (mm) SYSCW-AR R513A VC BA 1 138 716 105 821 260 236 242 8.
SYSCW-AR R513A Dimensions (mm) (continued) SYSCW-AR R513A VN BA 40 1 005 39 664 105 521.5 769 626.5 241 25 92 1 084 54 532 236 242 8.4 105 769 142.
SYSCW-AR R513A Dimensions (mm) (continued) SYSCW-AR R513A VC FA 1 138 8.
SYSCW-AR R513A Dimensions (mm) (continued) SYSCW-AR R513A VN FA 40 1 005 10 667.5mini / 697.5maxi 525mini / 555maxi 525mini / 555maxi 250 54 532 8.4 236 242 25 92 1 055 23 mini 53 maxi 667.5mini / 697.5maxi 142.
SYSCW-AR R513A Dimensions (mm) (continued) SYSCW-AR R513A VCL BA 260 8.
SYSCW-AR R513A Dimensions (mm) (continued) SYSCW-AR R513A VNL BA 17
SYSCW-AR R513A Dimensions (mm) (continued) SYSCW-AR R513A VCL FA 260 8.
SYSCW-AR R513A Dimensions (mm) (continued) SYSCW-AR R513A VNL FA 40 1 005 140 525mini / 555maxi 525mini / 555maxi 230 1 185 54 530 8.
20 SYSCW-AR Notes
Systemair AC SAS · route de Verneuil, 27570 Tillières-sur- Avre · Tél. 02 32 60 61 00 · Fax 02 32 32 55 13 Systemair · EDM CWAR 02-S-1GB/12.21 - Supersedes : None As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. www.systemair.