IOM SYSAER R32 (IOM SYSAER R32 01 N 2GB)
Table Of Contents
- COUVERTURE PREMIERE IOM AER32 01-EN.pdf
- IOM AER32 01-N-GB_text.pdf
- CONTENTS
- 1. GENERAL RECOMMENDATIONS
- 2. INSPECTION AND STORAGE
- 3. WARRANTY
- 4. PRESENTATION
- 5. CONTENTS Of PACKAGE
- 6. DIMENSIONS
- 7. HANDLING
- 8. TECHNICAL SPECIFICATIONS
- 9. CONFIGURATION OF THE UNIT
- 10. OPTIONS
- 11. INSTALLATION
- 12. HYDRAULIC LINKS
- 13. WIRING DIAGRAM AND LEGEND
- 14. ELECTRICAL CONNECTIONS
- 15. COMMISSIONING
- 16. FINAL TASKS
- 17. IN CASE OF WARRANTY - MATERIAL RETURN PROCEDURE
- 18. ORDERING SERVICE AND SPARE PARTS ORDER
- 19. MAINTENANCE
- 20. TROUBLE SHOOTING
- ANNEXE AER32 01-N.pdf
- COUVERTURE DERNIERE IOM AER32 01-EN.pdf
English
Fin edges are sharp and can cause injury hazard. Avoid contact with them.
Caution
Avoid damaging the aluminium ns during cleaning. Never use pressurized water without a wide
diffuser. Concentrated and/or rotating water jets are strictly forbidden.
Caution
39SYSAER R32
Clean the air exchanger using a special product for aluminium-copper coils and rinse with water. Do not use
hot water nor steam, as these may increase the refrigerating uid's pressure.
19.3.1.4. AIR COOLED CONDENSER
Condenser coils are composed of copper tubes and aluminium ns. In case of leaks due to damage or
shock, the coils must be repaired by one of the authorized Support Centres. To guarantee the best possible
operation of the condenser bank, the condenser surface must be maintained as clean as possible, and it
must be void of foreign materials (leaves, wires, insects, slag, etc.). A dirty coil will see its absorbed electrical
power increase. In addition, condensation pressure could increase and trigger a high pressure alarm.
CAUTION
BEFORE CARRYING OUT ANY OPERATION ON THE EQUIPMENT, CHECK
THAT THE ELECTRICAL POWER SUPPLY IS SWITCHED OFF AND THAT IT
CANNOT BE SWITCHED ON INADVERTENTLY.
IT IS RECOMMENDED THAT THE DISCONNECT SWITCH BE PADLOCKED