The frame of the curb receiving the unit must be leveled. The unit must slot perfectly into the roof
curb.
Caution
R1S1
B
180
C
A
23SYSAER R32
11.3. ATTACHMENT TO THE GROUND
The surface of the oor or structure located
under the SYSAER R32 must be at, and
with sufcient strength to withstand the
unit's weight, and occasional presence of
maintenance equipment.
For normal applications, rigidity of the SYSAER R32 and the positions of supports allow for an installation
minimizing vibrations. However, the installers can use anti-vibration rubber pads (supplied in option).
The SYSAER R32 does not require
anchoring on the foundations, except in
regions exposed to a high earthquake risk
or if the device is installed on a high level
on a steel frame.
When tting anti-vibration pads, refer to the manual supplied with the kit.
11.4. ROOF CURB
The main purpose of the roof curb is to provide
weatherproof passage, supply and return air down to the
building from the SYSAER R32.
All connections (air, electricity) will be protected against
adverse weather. Thanks to the roof curb, the sealing
and thermal insulation achieved by the installer and the
distribution of weight are perfect between the SYSAER
R32 and the roof.
The roof curb should be used for a downward
conguration at supply and return air. The roof curb
guarantees the perfect weathertight sealing between
the building structure and the appliance.
The roofcurb is factory assembled, and it must be
adjusted on site.
SEE APPENDIX
11.4.1. DIMENSIONS
A B C
mm mm mm
SR R32 105
SR R32 120
SR R32 140
base module
2 dampers
2 120 1 375 1 562
3 dampers 2 120 1 540 2 073