IOM SYSAER R32 (IOM SYSAER R32 01 N 2GB)

Table Of Contents
English
Never drill any holes in the air treatment zone of the unit. The manufacturer’s warranty WILL be
CANCELLED in the event of any water leaks resulting from the drilling of holes in the casing.
Caution
R1
S2
Information
The gas burner is only available in congurations:
² Downward discharge: S1
² Discharge from the rear: S3
R2
S2
17SYSAER R32
9. CONFIGURATION OF THE UNIT
9.1. GENERALITIES
The unit is designed to be connected to a duct work. The duct network pressure loss must be related to
available outdoor pressure of SYSAER R32.
4 discharges and 3 intakes air congurations are available.
For each conguration, note the dimensions of the discharge air duct to be provided before the unit arrives
on site. Make sure that it is reproof and that it does produce toxic smoke in the event of a re in the
building. The interior surfaces must be smooth and cleanable to avoid contamination of the circulated air.
To ensure itself of a good air tightness and to water enters the machine and the air duct.
9.2. SUPPLY AIR
² Downward discharge: S1
² Sideway discharge: S2
² Discharge from the rear: S3
² Top discharge: S4
9.3. AIR INTAKE
² Return air from below: R1
² Return air from the side: R2
² Return air from the top: R4
Lower blowing (S1) or lower air intake (R1) require
the presence of a roof curb. For other versions, given
the unit’s weight, analyse the installation to avoid any
risk of damage to the bracket on which the unit will
be placed.
SEE APPENDIX
9.4. DUCT OUTLET DIMENSIONS