The installer is responsible for ensuring that the cable
hole in the panel is sealed properly.
Caution
Correction of the excessive centralized power factor (>0.95) may generate transient phenomena
dangerous for the motors and contactors of the unit during the start and stop phases. Check
instant voltages during these phases.
Caution
B
A
C D
B
A
C D
29SYSAER R32
The electric connection of range RT is done in a single point on
the level of the principal circuit breaker.
Electrical power supply cable should be inserted by the base or
on the side of the unit.
Cable holes need to be drilled in the panel in relation to the
thickness of the power cables.
These units are equipped with a local switch used as general
terminal board.
The switch can be padlocked.
A circuit breaker or fuse holder (not supplied) must be installed on the main power supply of the unit in
accordance with the circuit diagram.
To ensure proper contact, t the end pieces adapted to the cross-section of the connecting cable.
A B C D
mm mm mm mm
SR R32 105
129 60 615 90
SR R32 120
129 60 615 90
SR R32 140
129 60 615 90
A B C D
mm mm mm mm
SR R32 105
624 69 213 259
SR R32 120
624 69 213 259
SR R32 140
624 69 213 259