Scroll Compressor Refrigerant R32 SYSAER R32 Rooftop Units - Heat Pump Version Models SR R32 105 - SR R32 120 - SR R32 140 106 to 139 kW 106 to 142 kW 19 200 to 25 500 m3/h R32
SYSAER R32 Key Points Energy class A, EC PLUG FAN for supply air and AC FAN for extract air, Ecodesign 2021, 2 filters stage R32 refrigerant, High SEER and SCOP, ² G4 2 circuits for the entire range to optimize performances at part load, and avoid cold draught during defrost mode. ² F7 / F9 1 energy recovery system ² The range SYSAER R32 is provided with 2 compressors, 1 per circuit.
2 SYSAER R32 Specifications General Compressors The new SYSAER R32 units have been designed and optimized to operate with R32 refrigerant fluid. They are of single refrigerant circuit type. Each unit is equipped with two scroll mono‑compressors fitted on a rail and assembled together to form tandem compressors. They are available in reversible version. The compressors are then mounted on rubber pads in order to eliminate noise and vibration transmissions.
SYSAER R32 Specifications Blast and return fan The SYSAER R32 is provided with blast and return fans, PLUG FAN type with an AC (Asynchronous) motor or with an EC (Electronic Switching) motor, Low Pressure or High Pressure according to the configuration selected by the customer. Economiser with 2 dampers The factory-mounted economiser with 2 dampers is available with the R1, R2 and R4 configurations.
4 SYSAER R32 Specifications Heating Frame The SYSAER R32 can be equipped, according to the specifications of the customer, with an additional heating system. This equipment is installed and tested in the factory. The mounting frame is made from galvanized steel sheet. It is delivered with a seal to connect the edge of the frame to the unit and eliminate vibrations and thermal bridges. Electric heating The electric heating battery is available on all of the configurations of the SYSAER R32.
SYSAER R32 Specifications Control The IATC is equipped with clock card for scheduler programming. This card can be programmed on site in comfort-economy modes with a reduction in the ambient temperature and in the ambient humidity. The user interface also contains a backlit semigraphic liquid crystal display screen with 8 lines and 22 columns. This display shows the current values, setpoints, operating times and alarms.
6 SYSAER R32 Models designation SR R32 105 . H . SYS . EH . G4 . EC HPF . S1 . R1D2 . HY . LK . + . AVM . SD 1 REP.
SYSAER R32 Refrigerant Flow Diagram SR R32 105 - SR R32 120 - SR R32 140 PTHP-1.1 PSHP-1.1 CDT-1.1 CDT-2.1 PSHP-2.1 RV-1.1 RV-2.1 OF-1.1 C-1.1 OF-2.1 C-2.1 PTLP-1.1 OAT-0.1 OCT-1.1 PTHP-2.1 PTLP-2.1 DF-1.1 SG-1.1 SG-2.1 DF-2.1 TEV-1.1 IC-0.1 OCT-2.1 TEV-2.1 AIR EXTRACTED RAT-0.1 IF-0.1 IF-0.2 OUTDOOR AIR SAT-0.1 RETURN AIR REPERE C1.1 / C1.2 C2.1 / C2.
8 SYSAER R32 Refrigerant Flow Diagram PTHP-1.1 PSHP-1.1 CDT-1.1 CDT-2.1 PSHP-2.1 RV-1.1 RV-2.1 OF-1.1 C-1.1 OF-2.1 C-2.1 PTLP-1.1 OCT-1.1 PTHP-2.1 PTLP-2.1 DF-1.1 SG-1.1 SG-2.1 DF-2.1 TEV-1.1 OCT-2.1 TEV-2.1 IC-0.1 FA-0.1 AIR EXTRACTED RAD-0.1 FM-0.1 RAT-0.1 OAD-0.1 RAH VOC/CO2 IF-0.1 IF-0.2 OAH OAT-0.1 OUTDOOR AIR SAT-0.1 RETURN AIR PTHP-1.1 SUPPLY AIR PSHP-1.1 CDT-1.1 CDT-2.1 PSHP-2.1 RV-1.1 RV-2.1 OF-1.1 C-1.1 OF-2.1 C-2.1 PTLP-1.1 OCT-1.1 PTLP-2.1 DF-1.
SYSAER R32 Aeraulic configuration AIR RETURN Compatible with economiser with 2 or 3 dampers R1 R1 FRESH AIR Compatible with economiser with 2 or 3 dampers R2 R2 FRESH AIR Compatible with economiser with 2 dampers R4 FRESH AIR 9
10 SYSAER R32 Aeraulic configuration AIR BLAST Compatible with gas burner S2 S1 Compatible with gas burner S4 S3
SYSAER R32 Energy performance Energy class More efficient A B C D E F G SYSAER R32 SR R32 105 SR R32 120 SR R32 140 EER 3.37 3.23 3.24 Class A A A Space cooling energy efficiency class according to EN 14511 2018. Less efficient More efficient A B C D E F G Less efficient SYSAER R32 SR R32 105 SR R32 120 SR R32 140 COP 3.72 3.89 3.69 Class A A A Space heating energy efficiency class according to EN 14825 2017.
SYSAER R32 Operating Limits Cooling mode Outdoor air temperature (°C db) 55 50 45 40 35 30 25 20 15 10 Using All Seasons Kit 5 0 -5 -10 -15 5 10 15 20 25 30 Temperature mix prior to internal coil (°C wb) Heating mode 20 Outdoor air temperature (°C db) 12 15 10 5 0 -5 -10 THERMO OFF CONDENSATION GAS HEATER OR HOT WATER COIL THERMO OFF ATMOSPERIC GAS HEATER OR HOT WATER COIL -15 -20 -15 -10 -5 0 5 10 15 Mixing temperature (°C db) 20 25 30
SYSAER R32 Correction Factors Fouling factors - Evaporator Fouling factor (m2.°C/kW) Capacity Power input 0.044 1.000 1.000 0.088 0.987 0.995 0.176 0.964 0.985 0.352 0.915 0.962 Fouling factors - Condenser Fouling factor (m2.°C/kW) Capacity Power input 0.044 1.000 1.000 0.088 0.987 1.023 0.176 0.955 1.068 0.352 0.910 1.135 Altitude (m) Capacity Power input 0 1.000 1.000 600 0.987 1.010 1200 0.973 1.020 1800 0.958 1.030 2400 0.943 1.
14 SYSAER R32 Physical Data - SYSAER R32 SR R32 105 SR R32 120 SR R32 140 106 31.5 3.37 A 106 3.80 149 106 27.0 3.72 A 100.00 3.36 / B 131.00 119 36.8 3.23 A 119 3.80 149 117 30.3 3.89 A 118.00 3.56 / B 130.00 139 43.0 3.24 A 139 3.67 144 142 38.0 3.69 A 140.00 3.32 / B 130.00 400V / 3 / 50Hz 79.00 284.00 85.00 288.00 105.00 346.
SYSAER R32 Weight basic Filter G4 G4+F7 G4+F9 2 dampers 3 dampers RECO Electric heating Warm water coil kg Kg kg kg Kg Kg Kg Kg SR R32 105 SR R32 120 SR R32 140 1 685 1 805 1 855 45 45 45 65 65 65 65 65 65 115 115 115 430 450 450 30 30 30 30 30 30 Electrical Data The maximum intensity absorbed by the SYSAER R32 as well as the total start-up intensity are calculated by adding the basic values provided for the SYSAER R32 with the additional options.
SYSAER R32 Dimensions (mm) 2150 SYSAER SR R32 105 - 120 - 140 - BASE MODULE / BASE MODULE WITH 2 DAMPERS 3295 3740 135 16 1506 2195 2285 2750
SYSAER R32 Dimensions (mm) 2150 SYSAER SR R32 105 - 120 - 140 - BASE MODULE R1 WITH 3 DAMPERS 135 3980 4430 1506 2195 2285 3040 17
SYSAER R32 Dimensions (mm) 2150 SYSAER SR R32 105 - 120 - 140 - BASE MODULE R2 WITH 3 DAMPERS 3980 4430 135 18 1506 2195 2285 2760
SYSAER R32 Dimensions (mm) 2285 SYSAER SR R32 105 - 120 - 140 - BASE MODULE WITH 2 DAMPERS AND GAS BURNER 135 3295 3892 1506 2195 2285 3040 19
SYSAER R32 Dimensions (mm) 2454 SYSAER SR R32 105 - 120 - 140 - BASE MODULE R1 WITH 3 DAMPERS AND GAS BURNER 3980 4566 135 20 1506 2195 2285 3042
SYSAER R32 Dimensions (mm) 2454 SYSAER SR R32 105 - 120 - 140 - BASE MODULE R2 WITH 3 DAMPERS AND GAS BURNER 135 3980 4566 1506 2195 2285 3058 21
SYSAER R32 Duct outlet dimensions (mm) AIR RETURN R1 - BASE MODULE OR 2 DAMPERS B D C A R1 SR R32 105 SR R32 120 SR R32 140 A mm 1 924 1 924 1 924 B mm 500 500 500 C mm 173 173 173 D mm 1 669 1 669 1 669 C AIR RETURN R1 - 3 DAMPERS D 22 A B SR R32 105 SR R32 120 SR R32 140 A mm 2 420 2 420 2 420 B mm 500 500 500 C mm 271 271 271 D mm 1 651 1 651 1 651 R1
SYSAER R32 Duct outlet dimensions (mm) D AIR RETURN R2 - BASE MODULE OR 2 DAMPERS C R2 B A 22 SR R32 120 SR R32 140 A mm 1 915 1 915 1 915 B mm 599 599 599 C mm 341 341 341 D mm 1 680 1 680 1 680 22 SR R32 105 AIR RETURN R2 - 3 DAMPERS C 22 D 22 B A SR R32 105 SR R32 120 SR R32 140 A mm 2 370 2 370 2 370 B mm 599 599 599 C mm 240 240 240 D mm 1 680 1 680 1 680 23
SYSAER R32 Duct outlet dimensions (mm) D C AIR RETURN R4 - BASE MODULE OR 2 DAMPERS 22 A B SR R32 105 SR R32 120 SR R32 140 A mm 1 865 1 865 1 865 B mm 581 581 581 C mm 316 316 316 D mm 1 750 1 750 1 750 22 AIR BLAST S1 B C A D 24 S1 SR R32 105 SR R32 120 SR R32 140 A mm 310 310 310 B mm 705 705 705 C mm 164 164 164 D mm 1 400 1 400 1 400
SYSAER R32 Duct outlet dimensions (mm) AIR BLAST S2 D S2 C 22 B 22 A SR R32 105 SR R32 120 SR R32 140 A mm 100 100 100 B mm 1 087 1 087 1 087 C mm 78 78 78 D mm 1 910 1 910 1 910 D AIR BLAST S3 WITHOUT GAS BURNER A B C S3 20 22 SR R32 105 SR R32 120 SR R32 140 A mm 320 320 320 B mm 1 086 1 086 1 086 C mm 77 77 77 D mm 1 911 1 911 1 911 25
SYSAER R32 Duct outlet dimensions (mm) D WITH GAS BURNER B A SR R32 105 SR R32 120 SR R32 140 C S3 A mm 172 172 172 B mm 1 287 1 287 1 287 C mm 77 77 77 D mm 1 069 1 069 1 069 20 22 AIR BLAST S4 S4 B C A D 26 22 22 SR R32 105 SR R32 120 SR R32 140 A mm 272 272 272 B mm 786 786 786 C mm 595 595 595 D mm 1 481 1 481 1 481
SYSAER R32 Space Requirements (mm) 2000 2000 2000 2000 2000 27
28 SYSAER R32 Notes
Systemair AC SAS · route de Verneuil, 27570 Tillières-sur- Avre · Tél. 02 32 60 61 00 · Fax 02 32 32 55 13 September 2021 Systemair · EDM AER R32-S-2GB/09.21 - Supersedes : EDM AER R32-S-1GB As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. www.systemair.