DataSheet TUNE R for AHU201710
2 / 4 | Air Volume Control
Description
The TUNE-R, circular single-blade dampers are mainly intended as a part of air handling units and fan systems to
cover the air ow tuning and tight shut-off functionalities. The dampers can be used in indoor and outdoor climate
conditions installed on the body of TUNE-R or fan or in the circular duct. They are equipped by electric actuator with
spring return to closed position in case of electric power interruption. Manual operation/adjustment is also possible.
They can operate in both directions of air ow. The air tightness of the dampers is classied as C4 according to the
standard EN 1751 in pressure range up to 1000 Pa which is the maximum recommended duct pressure for this
product. The operation temperature range is -20°C ... 100°C in duct, 50°C on actuator.
Design
TUNE-R dampers are constructed from galvanized steel sheet. The blade is equipped by rubber gasket eliminating
leakage in closed position. The blade shaft is sitting in self - lubricating polymeric bearings.
The connection of to the ductwork is sealed by rubber gaskets contributing to the casing tightness.
Controls/Wiring
Power supply: AC 24 V/50 - 60 Hz or DC 24 V
Power consumption: 5 W (DC), 6 VA (AC)
Mechanical protection: IP 54
q (m
3
/h)
CLOSE
OPEN
a b
21
a
b
-
⊥
~ AC 24 V
+ DC 24 V