HandBook F R60K2022 07 11

57/59 | F-R60K
Handling & Manipulation
Handling and manipulation must be done with care. For safety reasons manipulate the damper in its closed possition
and with gloves.
Operation Manual
Warning: Damper blades are spring loaded in the open position and are closing very quick. To avoid injury, make sure
to keep the blade movement area clear while manipulating with the fire damper.
After installation, it is necessary to adjust the damper into its operating position – open the fire damper.
Connect the electric driving mechanism to the relevant electric power supply (see Electrical connection section). The
electromotor is activated and adjusts the damper into its open position.
Functionality Check
While performing the check, focus on the thermal fuse link’s integrity and a correct position of the damper blades
after their detention in the OPEN and CLOSED positions.
The fire damper must open automatically after the actuator receives power – the arrow (P13) on the actuator axis in
open possition must point to 90°.
Press the control switch (P12) on the Thermo electric fuse and hold it until the fire damper is fully closed – the arrow
(P13) on the actuator axis in closed possition must point to 0° - safety possition.
Release the control switch (P12) on the Thermo electric fuse. The fire damper must become fully open – the arrow
(P13) on the actuator axis in open possition must point to 90° - operating position.
Test
Test
G230T, G...
Test
B230T, B...
90°
0°
Test
90°
0°
P13
P12
P13
P12