HandBook F R60K2022 07 11

51/59 | F-R60K
Baud
Parity
Term
Bus
ON
ON
OFF
MSB LSB
Address
WE ON WE
1 2 3 4 5 6 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7
BKN230-24-MOD
1
2
6
4
3
T
U
5
7
COM
A1 1 2
9600 OFF OFF
19200 OFF ON
38400 ON OFF
76800 ON ON
A2 3 4
1-8-N-1 OFF OFF
A3 5
150 Ω ON
OFF OFF
A4 6
BACnet ON
Modbus OFF
B 1 2 3 4 5 6 7 8
0 - OFF OFF OFF OFF OFF OFF OFF
1 - OFF OFF OFF OFF OFF OFF ON
2 - OFF OFF OFF OFF OFF ON OFF
... - - - - - - - -
127 - ON ON ON ON ON ON ON
Legend
U - USB mini socket: BKN-MOD-BAC Update Tool
T - Test button: Test run / fault acknowledgement. Press the button for longer than one second to trigger the start of
test run or to trigger a reset of present error message.
1 - Power supply: cable and plug, AC 230 V
2 - 3-pin connector: damper actuator (DC 24 V)
3 - 6-pin connector: damper actuator (position limit switches)
4 - 7-pin spring terminal:
• 1External smoke detector, +24 V, max. 50 mA