Type of activation BST2
IMPORTANT: Danger of electric shock!
Switch off the power supply before working on any electrical equipment.
Allow only qualified electricians to work on the electrical system.
Actuator power supply via fitted communication unit: DC 24 V
NOTES:
• Depiction of parts for fitted communication and supply unit BKN230-24-MOD (Modbus/BACnet).
6 - LEDs status indication of actuator
LED colour| LED state | Status
Green | ON | Damper open
Green | Blinks | Damper is opening
Yellow | ON | Damper closed
Yellow | Blinks | Damper is closing
Red | Blinks | Internal device fault (BKN230-24-MOD)
Red | Blinks | External fault: smoke detector triggered; nominal position not reached
Red | Flashes | External fault: If an error is stored (i.e. no longer pending, but not yet acknowledged), then this is
displayed on the device by a periodic flash of the red LED.
7 - LED signalization of communication unit (BKN230-24-MOD)
LED colour| LED state | Status
Command OPEN / limit position not reached:
Green | ON | -
Yellow | ON | Damper closed
Yellow | OFF | Damper blade is between close and open
Yellow | Flickering | BACnet/Modbus communication is illuminated during RX and TX
Red | Blinks | Error message after 180 seconds
Command CLOSE / limit position not reached:
Green | ON | Damper open
Green | OFF | Damper blade is between open and close
Yellow | Blinks | -
Yellow | Flickering | BACnet/Modbus communication is illuminated during RX and TX
Red | Blinks | Error message after 60 seconds