HandBook F R60K2022 07 11
47/59 | F-R60K
IMPORTANT:
If only one actuator is connected to the FSC-UFC24-2 the LEDs of the side where no actuator is connected indicate an
alarm. A jumper has to be installed between S4 and S6 in the terminal where there is no actuator connected, to
indicate an “opened” position in the LED. If the second connection is not activated via bus, there will be no alarm signal
on the bus system.
Legend
A1, A2 Analog Application; Digital input for manual override can be selected via bus as „Normally Open“ (= standard
open) or „Normally Closed“ (= standard closed) Default: „Normally Open“
B Position of line termination 120 ohm if FSC-UFC24-2 is last Modbus or BACnet device in line
C RS-485 Coms; Modbus RTU or BACnet MS/TP dip switch selectable
D1, D2 Damper 1, Damper 2; Fire or smoke extraction application
P Main power 24 V AC/DC; Daisy chain from and to other FS-UFC24-2
So Contact open
Sc Contact closed