HandBook F R60K2022 07 11
46/59 | F-R60K
Type of Activation GST0
• The actuator and the control module are factory wired.
• Individual control of 2 fire dampers
• Bus protocols (RS-485): BACnet MS/TP and Modbus RTU
• Automatic baud rate detection with BACnet
• Bus monitoring function
LEDs status indication (GST0)
LED color and type | LED state | Status
Yellow (Closed) | ON | Damper closed
Green (Open) | ON | Damper open
Yellow and green | Blinks in parallel | Damper is moving
Yellow and green | Alternately blinks - interval 0.5 sec | Actuator did not reach the end switch position within set time
Yellow and green | Alternately blinks - interval 3 sec | Alarm active at damper: bus command = actuator open, actuator
= in closed position
Power green | OFF | Power failure
Power green | ON | Power is connected
Yellow Rx | Blinks | Receive data
Green Tx | Blinks | Transmit data
Notes:
• Caution! Main power supply voltage!
• Power consumption and switching thresholds must be observed!
• Combination of power supply voltage and safety extra-low voltage not permitted at the both auxiliary switches.