Type of Activation G230T
IMPORTANT: Risk of electric shock!
Switch off the power supply before working on any electrical equipment.
Only qualified electricians are allowed to work on the electrical system.
Actuator power supply: 230V AC, 50/60 Hz
Notes:
A device that disconnects the pole conductors (minimum contact gap 3 mm) is required for isolation from the power
supply.
Parallel connection of several actuators possible.
Power consumption must be observed!
Legend
1 - Blue cable colour
2 - Brown cable colour
S1 - Violet cable colour
S2 - Red cable colour
S3 - White cable colour
S4 - Orange cable colour
S5 - Pink cable colour
S6 - Grey cable colour
Tf - Thermal fuse