HandBook F R60K2022 07 11

35/59 | F-R60K
Electrical Connections
IMPORTANT
Danger of electric shock!
Switch off the power supply before working on any electrical equipment.
Only qualified electricians are allowed to work on the electrical system.
Actuator Size Map
A
DN (mm)
100 125 140 150 160 180 200 225 250 280 315 355 400 450 500 560 630
Belimo BFL-T-... / Gruner 340TA--05 Belimo BFN-T-... / Gruner 360TA--12
Electrical Parameters per Activation and Actuator Type
AT A T
(Nm)
NV
(V)
F
(Hz)
CO CR
WS
(VA)
WN
(W)
B230T
BFL230-T 4 AC 230
50/60
3,5 1,1 6,5 Imax 4 A @ 5 ms
BFN230-T 9 AC 230 9 2,1 10 Imax 4 A @ 5 ms
G230T
340TA-230--05- 5 AC 230 5,5 2 9,5 -
360TA-230--12- 12 AC 230 5,5 1,5 11,5 -
BST0
BFL24-T-ST & BKN230-24 4 AC 230 10 3,5 11 Imax 4 A @ 5 ms
BFN24-T-ST & BKN230-24 9 AC 230 10 3,5 11 Imax 4 A @ 5 ms
GST0
340TA-24--05-.../ST01
& FSC-UFC24-2
5 AC/DC 24 8,5 4 11 -
360TA-24-12-.../ST01
& FSC-UFC24-2
12 AC/DC 24 7 4 9 -
B24T,
B24T-W
BFL24-T, BFL24-T-ST 4 AC/DC 24 2,5 0,8 4 Imax 8,3 A @ 5 ms
BFN24-T, BFN24-T-ST 9 AC/DC 24 4 1,4 6 Imax 8,3 A @ 5 ms
G24T,
G24T-W
340TA-24--05-...
340TA-24--05-.../ST01
5 AC/DC 24 6,5 2 9 -
360TA-24--12-...
360TA-24--12-.../ST01
12 AC/DC 24 5 2 7 -
B24T-SR
BFL24-SR-T 4 AC/DC 24 3 1 6,5 Imax 8,3 A @ 5 ms
BFN24-SR-T 9 AC/DC 24 4,5 1,7 8,5 Imax 8,3 A @ 5 ms
G24T-SR
340CTA-24--05- 5 AC/DC 24 6,5 2 7,5
DC (0)2 V ...10 V
/ Ri > (100 kΩ)
50 kΩ (0)4 ... 20 mA
360CTA-24--12- 12 AC/DC 24 5 2 7
Notes
AT - Activation type
A - Belimo Actuator type
T - Torque
NV - Nominal Voltage
F - Frequency
CO - Consumption in Operation
CR - Consumption in Rest
WS - Wire sizing consumption