HandBook F R60K2022 07 11

30/59 | F-R60K
Legend for Installation OUT of the Standard Wall
F1 - Screw d=4; e.g. DIN7981
F2 - Fire resistive coating, Kleber K84/Promat or Grena-klebepaste/Grena
F3 - Mineral wool filling (min. 100 kg/m^3)
F5 - L-profile 25x25x3 or part of accessory R1-F-R60K ringlet
F6 - Self taping screws d=4.2
F7 - M10 Steel threaded rod + M10 nuts (2x on each rod)
F8 - Stone wool PAROC Pro Wired Mat 80 AL1 (PAROC), thickness 70 mm, nominal density 80 kg/m^3; Binding wires
or wire clamps.
F9 - Aluminium tape
1 - Fire damper (F-R60K)
2 - Bendable hanger
A1 - Ringlet UVH30 (Lindab) or Accessory: R1-F-R60K ringlet for Out installation.
3 - Concrete/masonry/cellular concrete wall or ceiling.
4 - Flexible (plasterboard) wall
4a - 2 layers of plasterboard fireproof plate type F, EN 520
4b - Vertical CW – profiles
4c - Horizontal UW – profiles
4d - Mineral wool; thickness/cubic density see picture.