HandBook F R60K2022 07 11
3/59 | F-R60K
Fire Damper with Quick Mount Kit
Description
Fire dampers represent passive fire protection, designed with the help of compartmentalization to prevent the spread
of toxic gases, smoke and fire. The opening and closure of the damper blade can be activated remotely. In case of fire,
when the air in the duct exceeds 72 °C, the thermal fuse melts. Melting of the thermal fuse activates the closure of
the damper blade automatically. Damper blade is then mechanically locked in closed position.
Highlights
• Greatly reduced installation time
• 100 mm body length
• On & out of shaft wall installations
• Easy actuator and unit access
• Casing leakage according to EN 1751, class B
• Blade leakage according to EN 1751, class 3










