HandBook F R60K2022 07 11

13/59 | F-R60K
Installation Methods
ON
F-R60K
DN100 ... DN630
EI 60 (v
e
- i o) S
a) b)
360°
100 mm 100 mm
d)
80 mm
EI 60 (h
o
- i o) S
c)
100 mm
620 kg/m
3
OUT
F-R60K
DN100 ... DN630
EI 60 (v
e
- i o) S
a) b)
360°
100 mm 100 mm
d)
80 mm
Notes:
a) - Flexible (plasterboard) wall
b) - Concrete/masonry/cellular concrete (rigid) wall
c) - Concrete/cellular concrete (rigid) floor/ceiling
d) - Shaft wall - one side covered with 2 layers of gypsum board
v
e
- Vertical wall placement
h
o
- Horizontal floor/ceiling placement
Installation Rules
The duct connected to the fire damper must be supported or hung in such a way that the damper does not carry its
weight. The damper must not support any part of the surrounding construction or wall which could cause damage
and consequent damper failure.
Easy access to mechanism and internal parts during inspection must be considered during damper placement.
According to the standard EN 1366-2, the distance between the fire damper bodies must be at least 200 mm.
The distance between the adjacent wall/ceiling and the damper must be at least 75 mm.
When the damper is installed into a fire partition structure, it must be placed so that the damper blades in its closed
position are located inside this structure.