DeclarationOfPerformance F R60K A

2/3 | F-R60
9. Declared performance:
Installations:
1 Wet
F-R60
DN100 ... DN400
EI 60 (v
e
- i o) S
a) b)
360°
100 mm 100 mm
EI 90 (h
o
- i o) S
c)
125 mm
( 620 kg/m
3
)
3 Soft
F-R60
DN100 ... DN400
EI 60 (v
e
- i o) S
a) b)
360°
100 mm 100 mm
EI 60 (h
o
- i o) S
c)
125 mm ( 620 kg/m
3
)
110 mm ( 2200 kg/m
3
)
3H Hilti
F-R60
DN100 ... DN400
EI 60 (v
e
- i o) S
a) b)
360°
100 mm 100 mm
EI 60 (h
o
- i o) S
c)
125 mm
( 620 kg/m
3
)
Legend:
1.Wet - Wet Installation, Using Plaster/Mortar/Concrete Filling
3.Soft - Soft Installation, Using Mineral Wool filing
3H.Hilti - Filling made only from Hilti foam
a) - Flexible (plasterboard) wall
b) - Concrete/masonry/cellular concrete (rigid) wall
c) - Concrete/cellular concrete (rigid) floor/ceiling
v
e
- Vertical wall
h
o
- Horizontal floor/ceiling