Instruction DVG EC controller

© 2019 OJ Electronics A/S
11
INSTRUCTIONS OJ-DV | Installation
11. Mechanical installation
Warning
Incorrect mechanical installation may cause overheating and impaired performance.
OJ-DV must only be installed by trained/experienced personnel.
To ensure proper cooling of the OJ-DV, it must be positioned in such a way that the passing air
flow (> 3 m/s turbulent air speed) can cool the OJ-DV cooling fins. (3 m/s turbulent air speed is
equivalent to 6.5 m/s laminar air speed). If the OJ-DV is installed in a reduced air flow (< 3 m/s
turbulent air speed) or mounted outside a direct airstream, the output power (kW) will be reduced.
External on-board cooling fan can be added.
Only OJ-DV-1013 can be installed without considering the above requirements for sucient air
flow over the cooling fins. OJ-DV-1013 is supplied with extra large cooling fins and can therefore
be mounted in still air with an air temperature of max. 40°C.
See Section 25: Technical Specifications.
To facilitate future service and maintenance tasks, ensure that there is sucient space around the
unit after it has been installed.
To achieve the specified enclosure rating, the cable glands must not point upwards (see fig. 11.2).
To prevent water from entering OJ-DV via cables and cable glands, ensure that connection is
performed in such a way that water is prevented from accumulating around the cable in the gland.
See fig. 11.3.
Check that the surface to which OJ-DV is attached is capable of supporting the entire weight of
the unit.
OJ-DV can be mounted vertically, horizontally or at an incline. See fig. 11.2.
OJ-DV must be installed on a flat solid surface.
To avoid unnecessarily long motor cables (max. 5 m), OJ-DV should be installed as close to the
motor as possible.
Use only the pre-cut installation holes/screw holes to secure OJ-DV in place.
Dimensioned drawings, see figs 10.2 to 10.6.
The OJ DV is not intended to be installed in direct sunlight. The plastic cover and glands are not
UV resistance approved. For installation outdoor it shall be ensured that the DV is protected from
direct sunlight.
For guidance for a UV cover the sketch below can be used.
Table 11. 1
DV housing size A [mm] B [mm] C [mm] D [mm]
H1 150 ≥ 195 ≥ 110 10
H1x 150 ≥ 195 ≥ 145 10
H3 150 ≥ 195 ≥ 120 10
H4 130 ≥ 230 ≥ 154 10
H5 165 ≥ 254 ≥ 154 10
Figure 11.1
BR1014A44a