ANS 1 Datasheet
HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com
E-Mail: info@regincontrols.com
Revision 2017-02-28
— 1 —
ANS-1
ANS-1
2 pressure outlets and 2 m plastic tube
Outlets for measuring pressure in a ventilation duct.
9 Plastic
9 60° angle at the tip
Function
For optimal measuring results, measuring points with
turbulent air flow should be avoided. Preferably, measur-
ing should be performed at a distance of 2 duct diameters
before bends and branching and at 6 duct diameters after
bends and branching.
Mounting
The pressure outlet shall be mounted so the arrow on the
outlet corresponds with the air flow through the duct .
Dimensions
ø 25
ø 16
ø 3.4
ø 6
ø 6.5
80 18.5
60°
Measurements in mm