Modbus Parameter Specifications
Table Of Contents
- Change history
- 1 Protocol frame
- 2 Holding registers
- 2.1 Overview
- 2.2 Reset
- 2.3 Set value
- 2.4 Password
- 2.5 Factory setting Control
- 2.6 Customer setting Control
- 2.7 Operating hours counter
- 2.8 Operating minutes counter
- 2.9 Addressing on/off
- 2.10 Stored set value
- 2.11 Enable RS485
- 2.12 Fan address
- 2.13 Set value source
- 2.14 Preferred running direction
- 2.15 Store set value
- 2.16 Mode of operation
- 2.17 Direction of action
- 2.18 Control parameters
- 2.19 Maximum modulation level
- 2.20 Minimum modulation level
- 2.21 Motor stop enable
- 2.22 Starting modulation level
- 2.23 Maximum permissible modulation level
- 2.24 Minimum permissible modulation level
- 2.25 Maximum speed
- 2.26 Maximum permissible speed
- 2.27 Ramp-up/ramp-down curve
- 2.28 Speed limit
- 2.29 Input characteristic curve
- 2.30 Maximum power
- 2.31 Maximum permissible power
- 2.32 Speed monitoring speed limit
- 2.33 Sensor actual value source
- 2.34 Interface settings
- 2.35 Rotating direction fail-safe mode
- 2.36 Fail-safe set value source
- 2.37 Set value for fail safe function
- 2.38 Time lag fail-safe speed
- 2.39 Cable break detection voltage
- 2.40 Sensor
- 2.41 Enable source
- 2.42 Stored enable RS485
- 2.43 Customer data
- 2.44 Error history
- 2.45 DC-link voltage reference value
- 2.46 DC-link current reference value
- 2.47 Manufacturing data
- 2.48 Air flow reference value
- 2.49 Mass flow reference value
- 2.50 Mirror function for holding registers
- 2.51 Mirror function for input registers
- 2.52 Mass flow calculation
- 3 Input registers
- 3.1 Overview
- 3.2 Identification
- 3.3 Maximum number of bytes
- 3.4 Bus controller software name
- 3.5 Bus controller software version
- 3.6 Commutation controller software name
- 3.7 Commutation controller software version
- 3.8 Actual speed
- 3.9 Motor status
- 3.10 Warning
- 3.11 DC-link voltage
- 3.12 DC-link current
- 3.13 Motor temperature
- 3.14 Temperature inside electronics
- 3.15 Current modulation level
- 3.16 Current set value
- 3.17 Sensor actual values
- 3.18 Enable input state
- 3.19 Current controller function
- 3.20 Current power
- 3.21 Current set value source
- 3.22 Energy consumption counter
- 3.23 Heartbeat
- 3.24 Mirrored input registers
MODBUS ACE V1.00
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 10/6/2003 ·File: ext001931381.docx ·Last printed 9/30/2019 10:29:00
AM ·Page 77 of 78
Form 1003
3.20 Current power
3.20.1 Relative coding
Address : D021
Coding:
DC-link voltage reference value (holding register D1A0)
DC-link current reference value (holding register D1A1)
3.20.2 Absolute coding W
Address : D027
Coding:
The numerical value of the input register corresponds directly to the current power in W
Further calculation using the reference values for DC-link voltage and DC-link current is not necessary.
3.21 Current set value source
Address : D028
This parameter indicates which set value source is currently being used.
The set value source depends on the parameter Set value source (holding register D101).
The set value source can also be influenced by the fail-safe function.
Coding:
Value
Set value source
0
Analog input Ain1
1
RS485 / Set value parameter (holding register D001)
255
Fail-safe function set value