Modbus Parameter Specifications

Table Of Contents
MODBUS ACE V1.00
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 10/6/2003 ·File: ext001931381.docx ·Last printed 9/30/2019 10:29:00
AM ·Page 76 of 78
Form 1003
3.18 Enable input state
Address : D01C
This parameter indicates the state of the Enable input.
The state of the Enable input depends on the holding registers Enable source and Enable RS485.
Coding:
Value
Enable
0
Enable off (motor stop)
1
Enable on (motor start permitted)
3.19 Current controller function
Address : D01E
This parameter indicates which controller function is currently being used.
The controller function depends on the controller function (holding register D108) and the currently selected
mode of operation (holding register D106).
Coding:
Value
Controller function
0
Positive: Deviation = Set value - Actual value
1
Negative: Deviation = Actual value - Set value
Notes:
For sensor control with a temperature sensor a positive controller function is synonymous with "Heating" and
a negative controller function is synonymous with "Cooling".