3.17.5 Air flow
Address m³/h : D033
Address coded relatively : D035
Coding m³/h:
󰇗


In unsigned integer format
Coding coded relatively:
󰇗



󰇗

󰇗

Air flow reference value (holding register D1ED)
The limit for the relative coded value is 65535.
3.17.6 Mass flow
Address kg/h : D034
Address coded relatively : D036
Coding kg/h:
󰇗


In unsigned integer format.
Coding coded relatively:
󰇗



󰇗

󰇗

Mass flow reference value (holding register D1EE)
The limit for the relative coded value is 65535.
3.17.7 Temperature PT1000
Address of PT1000 1 : D038
Address of PT1000 2 : D039
Depending on the configuration, the electronics enable up to two PT1000 temperature sensors to be
connected and evaluated. The measuring range of the temperature sensors is defined from -40°C to +250°C.
Outside this measuring range, a value of 32767 is given
Coding:


In signed integer format.