3.8 Actual speed
Address : D010
Coding:
The actual speed is obtained from the speed parameter and the maximum speed:





nMax [rpm] Maximum speed (in revolutions per minute)
Note:
If the actual speed exceeds the value "1.02 * Maximum speed", the display is limited to the
value "1.02 * Maximum speed" (0xFF00)
3.9 Motor status
Address : D011
The motor status indicates current fan errors.
Coding:
MSB
0
0
0
UzLow
0
0
0
0
LSB
BLK
0
TFM
FB
SKF
0
0
0
If a bit is set, the error described below has occurred:
UzLow: DC-link undervoltage
BLK: Motor blocked
TFM Motor overheated
FB: Fan Bad (general error)
*)
SKF: Communication error between master controller and slave controller
*)
"Fan Bad" is set for every error